Warning – Dunkirk Q95M-200 Modulating Condensing Boiler User Manual

Page 8

Advertising
background image

6.2 Combustion Air and Vent Pipe Requirements

• This boiler requires dedicated direct vent system.
• In direct vent system all air for combustion is taken

directly from outside atmosphere, and all flue products

are discharged to outside atmosphere.

• Combustion air and vent pipe connections must

terminate together in same atmospheric pressure

zone, either through roof or sidewall (roof termination

preferred). See Figures 5 and 6

for required clearances.

For proper set up of concentric vent termination see

Figure 7 and Figure 8.

WARNING

Solvent cements are combustible. Keep away from

heat, sparks, and open flame. Use only in well

ventilated areas. Avoid breathing in vapor or allowing

contact with skin or eyes. Failure these instructions

could result in fire, personal injury, or death.

!

• Locate combustion air inlet as far away as possible

from swimming pool and swimming pool pump house.

• All combustion air and vent pipes must be airtight and

watertight. Combustion air and vent piping must also

terminate as shown in “Combustion Air and Vent Pipe”

section.

• Vent connections serving appliances vented by

natural draft shall not be connected into any portion

of mechanical draft systems operating under positive

pressure.

• Covering non-metallic vent pipe and fittings with

thermal insulation shall be prohibited.

6 - LOCATING THE BOILER

6.3 Condensate Drain Requirements

• Condensate trap provided with boiler, an additional

trap is not required and should not be used.

• Pitch condensate drain line down to floor drain at

minimum of ¼” per foot. External condensate pump

(not furnished) may be used if floor drain is not

available.

• Condensate pump must be designed for flue gas

condensate application.

• Wood frame or blocks may be used to raise boiler

to maintain drain pitch or to be above external

condensate pump reservoir.

• If boiler is not level, condensate drain lines will not

function properly. Adjustable feet are located on boiler

to make up for minor surface irregularities or tilt.

• 115 volt AC receptacle provided on control panel to

provide power for external condensate pump if used.

6.4 Removal of Existing Boiler From Common

Vent System

When an existing boiler is removed from a common

venting system, the common venting system is likely to be

too large for proper venting of the appliances remaining

connected to it. At the time of removal of an existing boiler,

the following steps shall be followed with each appliance

remaining connected to the common venting system

placed in operation, while the other appliances remaining

connected to the common venting system are not in

operation.

1.

Seal any unused openings in the common venting

system.

2.

Visually inspect the venting system for proper size and

horizontal pitch and determine there is no blockage, or

restrictions, leakage, corrosion and other deficiencies

which could cause an unsafe condition.

3.

In-so-far as is practical, close all building doors and

windows and all doors between the space in which the

appliances remaining connected to the common venting

system are located and other spaces of the building.

Turn on clothes dryer and any appliance not connected

to the common venting system. Turn on any exhaust

fans, such as range hoods and bathroom exhaust, so

they will operate at maximum speed. Do not operate a

summer exhaust fan. Close fire dampers.

4.

Place in operation the appliance being inspected.

Follow the lighting instructions. Adjust thermostat so

appliances will operate continuously.

5.

Test for spillage at the draft hood relief opening after 5

minutes of main burner operation. Use the flame of a

match or candle, or the smoke from a cigarette, cigar

or pipe.

6.

After it has been determined that each appliance

remaining connected to the common venting system

properly vents when tested as outlined above, return

doors, windows, exhaust fans, fire place dampers,

and any other gas-burning appliance to their previous

condition of use.

7.

Any improper operation of the common venting system

should be corrected so the installation conforms with

the National Fuel Code, NFPA-54/ANSI -Z223.1 and/or

the Natural Gas and Propane Installation Code, CAN/

CSA B149.1. When re-sizing any portion of common

venting system, common venting system should be re-

sized to approach minimum size as determined using

appropriate tables in Chapter 13 of the National Fuel

Gas Code, NFPA-54/ANSI- Z223.1 and/or the Natural

Gas and Propane Installation Code, CAN/CSA B149.1.

8

Advertising