4 - boiler ratings & capacities 5 – Dunkirk Q95M-200 Modulating Condensing Boiler User Manual

Page 5

Advertising
background image

TABLE 1: SEA LEVEL RATINGS - NATURAL AND PROPANE GASES

Input (MBH)

(1)

Heating Capacity

(MBH)

(1)(2)

Net AHRI Rating

(MBH)

(1)

AFUE

(2)

Flue Diameter

Shipping Wt.

High Fire

200

182

158

92.5%

2” CPVC & 3” PVC

284 lbs.

Low Fire

80

73

63

(1)

1 MBH = 1,000 BTUH (British Thermal Units Per Hour)

(2)

Heating Capacity and AFUE (Annual Fuel Utilization Efficiency) are based on DOE (Department of Energy) test procedures.

TABLE 2: 95M-200 HIGH ALTITUDE DERATE CHART

Input

(MBH)

Altitude (In Feet)

3,000

(2)

4,000

(2)

5,000

(3)

6,000 7,000 8,000

9,000 10,000

High Fire

196

192

177

174.5

172

169

168

167

Low Fire

78.4

76.8

115

113.5

112

110

109

108

1)

Boiler Input Rate is determined at minimum vent length. The rate will decrease as vent length increases.

2)

Parameter 17 is set to 2,250 at elevations of 2,000 feet and below.

3)

Parameter 17 must be raised to 3,200 at altitudes or elevations of 2,000 feet and above.

• Heating Capacity indicates amount of heat available after subtracting losses up the stack. Most of this heat is available

to heat water. Small portion is heat loss from jacket and boiler surfaces, and it is assumed this heat stays in the

structure.

• Net AHRI Rating represents portion of remaining heat that can be applied to heat radiation or terminal units (i.e.,

finned tube baseboard, cast iron radiators, radiant floor, etc.) Difference between Heating Capacity and Net AHRI

Rating, called piping and pickup allowance, establishes reserve for heating volume of water in the system and

offsetting heat losses from piping.

• Net AHRI Ratings shown are based on piping and pickup factor of 1.15 in accordance with AHRI Standard. Net AHRI

Rating of selected boiler should be greater than or equal to calculated peak heating load (heat loss) for building or

area(s) served by boiler and associated hot water heating systems. Consult manufacturer before selecting boiler for

installations having unusual piping and pickup requirements.

4 - BOILER RATINGS & CAPACITIES

5