8 - COMBUSTION AIR AND VENT PIPE

Allowable Vent and Air Intake Lengths

3” Pipe Min. Length

3” Pipe Max. Length

15 ft. equivalent length

100 ft. equivalent length

FIELD INSTALL 2” BY 3”

TRANSITION IN THE

VERTICAL POSITION

ONLY (2 REQ’D, NOT

FURNISHED)

3” INTAKE AND

EXHAUST

TERMINATIONS

2” (50.8MM)

CPVC

VENT PIPING

(FURNISHED &

REQUIRED)

2” (50.8MM)

COMBUSTION AIR

INTAKE PIPING

(FURNISHED)

Figure 4 - Combustion Air & Vent Piping

9.

Combustion air must be clean outdoor air. Do not take

combustion air from inside structure because that air

is frequently contaminated by halogens, which includes

fluorides, chlorides, phosphates, bromides and iodides.

These elements are found in aerosols, detergents,

bleaches, cleaning solvents, salts, air fresheners, paints,

adhesives, and other household products.

10.

Locate combustion air inlet as far away as possible from

swimming pool and swimming pool pump house.

11.

All combustion air and vent pipes must be airtight and

watertight.

12.

Pitch exhaust air piping back to boiler at minimum ¼” per

foot from vent terminals so all moisture in vent piping

drains to boiler. Pitch pipes with no sags or low spots

where moisture can accumulate and block flow of flue gas.

13.

Vent connections serving appliances vented by

natural draft shall not be connected into any portion

of mechanical draft systems operating under positive

pressure.

8.2 Vent/Air Intake Termination Location

Consider following when determining appropriate location

for termination of combustion air and vent piping.

A. Position termination where vent vapors will not

damage plants/shrubs, air conditioning equipment, or

siding on the house.

B. Position termination so it will not be effected by wind

eddy, air born leaves, snow, or recirculated flue gases.

C. Position termination where it will not be subjected to

potential damage by foreign objects, such as stones,

balls, etc.

D. Position termination where vent vapors are not

objectionable.

E. Put vent on wall away from prevailing winter wind.

Locate or guard vent to prevent accidental contact

with people or pets.

F. Terminate vent above normal snow-line. Avoid locations

where snow may drift and block vent. Ice or snow may

cause boiler to shut down if vent becomes obstructed.

G. Under certain conditions, flue gas will condense,

forming moisture, and may be corrosive. In such

cases, take steps to prevent building materials at

vent from being damaged by exhaust of flue gas.

H. United States - Terminate vent system at least 4

feet (1.22 m) horizontally from, and in no case

above or below, unless a 4 feet (1.22 m) horizontal

distance is maintained, from electric meters, gas

meters, regulators and relief equipment.

I. Canada - Terminate vent system at least 6 feet

(1.83m) horizontally from, and in no case above

or below, unless 6 feet (1.83m) horizontal distance

is maintained, from electric meters, gas meters,

regulators and relief equipment.

J. Terminate venting system at least 3 feet (0.3m)

above any forced air inlet (except boiler’s

combustion air inlet) within 10 feet (3m).

K. Terminate venting system at least 12 inches

(300mm) from any air opening into any building.

L. Locate bottom of vent at least 12 inches (300mm)

above grade.

M. Terminate vent not less than 7 feet (2.1m) above

adjacent public walkway.

N. Vent terminal shall not be installed closer than 3 feet

(0.9m) from inside corner of L shaped structure.

O. Termination of vent should be kept at least 3 feet

(0.9m) away from vegetation.

P. If multiple terminations are used, minimum of

12 inches (300 mm) between exhaust of one

termination and air intake of next termination. See

pages 14 & 15.

Q. All field installed vent pipe must be 3”.

Length of pipe is counted from end of supplied 2” CPVC

pipe exiting boiler. Termination is not counted in “Total

Equivalent Length.”
Reduce maximum vent/air intake length by 5 feet per each

90° elbow.

WARNING

Covering non-metallic vent pipe and fittings with

thermal insulation shall be prohibited.

!