Dunkirk Q95M-200 Modulating Condensing Boiler User Manual

Page 21

Advertising
background image

Refer to Repair Parts Manual for illustrations, and Control

Manual and Troubleshooting Guide for detailed sequence of

operation and troubleshooting guide.

11.1 Aluminum Heat Exchanger

• Monoblock design cast aluminum heat exchanger

eliminates need for mating sections eliminates leaks

between sections.

• Cast aluminum has better heat transfer properties

which leads to higher efficiency and cooler exhaust

temperatures.

• Cooler exhaust temperatures create condensation of

flue gas, which would cause corrosion in traditional cast

iron heat exchangers.

11.2 Main Power Switch

Main power switch is located on the display panel. Main power

switch is illuminated when receiving power and in ON position.

11.3 Modulating Boiler Control

Integrated modulating control senses load necessary

to heat structure and therefore uses less fuel than

conventional fixed firing rate boiler when there is lower

than peak demand for heat.
Control senses supply water, return water, and outside

air temperatures. If outside air sensor is connected and

calculates load on system it adjusts firing rate to deliver

amount of heat needed at that particular time.

11.4 NTC Sensors

NTC sensors measure supply water, return water, and

outside air temperature. Configured to operate with

modulating boiler control.

11.5 Modulating Blower

• Modulating blower provides introduction of gas/air

mixture through burner and into combustion chamber

then out exhaust vent where combustion products are

discharged to outdoors.

• Blower is designed to communicate with modulating

control to run at variable speeds dependent on heating

system heat load.

• Variable speeds create pressures felt by gas valve and

gas/air mixer that dictate how much fuel is introduced
to combustion process.

11.6 Gas Control Valve

• Boiler gas controls have been developed for domestic

heating appliances with premix burners and automatic

direct burner ignition and are suitable for natural and

LP gas.

• Gas controls perform all functions required to safely

regulate gas flow to main burner of boiler.

• Gas valve is directly connected to gas/air mixer.

11.7 Gas/Air Mixer

Venturi design of gas/air ensures correct mixture of air and
gas.

11.8 Modulating Burner

Burner is designed to operate over full range of input.

Burner can operate under normal (blue flame) and infrared
conditions.

11.9 Direct Spark Igniter (DSI)

Boiler uses DSI to ignite fuel/air mixture in combustion

chamber and sense flame during operation. DSI is durable,

reliable, and resists breakage.

11.10 Manual Reset Low Water Cut Off

• Installed integral low water cut off (LWCO) must be

manually reset if there is a low water condition.

• LWCO senses water through probe at boiler top that

sends signal through water to ground. If the signal is

not sensed LWCO enters lockout mode that disables

boiler.

• LWCO in normal mode illuminates red indicator light on

LWCO panel in boiler.

• During low water condition, red light goes out and

LWCO and control reset buttons on display panel must

be pressed to reset LWCO.

11.11 Normally Closed LWCO Switch

• Round button switch located next to digital display is

normally closed and spring loaded, when depressed will

open, when pressure is removed closes.

• Switch is used as manual reset for LWCO. LWCO will

remain in lockout when tripped until water level reaches

probe and switch is pressed to open state and then

released to closed state, which sends signal to LWCO to

resume normal operation.

• Boiler control reset button must then be pressed to

reset from low water condition. LWCO switch and

control reset button are located on boiler panel display.

11.12 High Limit Control

• High limit control is safety limit control provides

protection for boiler and heating system from unsafe

operating conditions which could damage the boiler.

11 - CONTROLS AND ACCESSORIES