Dhw circ, Appendix a - boiler piping and wiring – Dunkirk Q95M-200 Modulating Condensing Boiler User Manual

Page 35

Advertising
background image

COMMON

ZONE MODULE

TO EXTRA

24 VAC

@ 1VA

PRIORITY ON

Hotline indirect water heater

ZR-ZC

CONTROL WITH

PRIORITY

120V AC

L2 N

L1 (HOT)

ISOLATED

CH C1

L1

SWITCH

X X

ZC

ARM-4P

X-X

DATA PORT

CIRC 3

ZONE 3

ZR

L

1

N

ZONE 2

CIRC 2

L

2

N

L

N

CIRC 4

3

N

4

ZONE 4

L

120 VAC

L

N

ZONE 3

T-STAT

THERMOSTATS

ZONE 3

ZONE 1

ZONE 2

PRIORITY

T

W

ZONE

1

T

R

ZONE 2

T-STAT

T

W

2

T

R

T

W

ZONE 4

T-STAT

T

3

R

ZONE 4

W

T

4

R

T

DHW CIRC

L2

CH C2

DHW C2

DHW C1

DHW T2

A2

A1

DHW T1

CH T2

CH T1

OUTDOOR

AIR SENSOR

aquastat or thermostat

Boiler Control Panel

115 V COIL / ISOLATION RELAY

NORMALY OPEN

NOTE: IN PLACE OF 115

VOLT ISOLATION RELAY,

OPTIONAL CONTROL

ARGO AR822II

TERMINAL 5 & 6 N.O.

TO DHW T1 & DHW T2

L1 & L2 TO ARM L &

N ON PRIORITY ZONE

ELEC

TR

ONIC FUSE

VAC

CIR

CUIT ON

120

L2

NO

4

NC

4

AR822-TT

SCREWS

TORQUE TERMINAL

6 TO 7 INCH LBS

TT

T

T
R W

24V

C 5 6

NO

6

NC

APPENDIX A - BOILER PIPING AND WIRING

Wiring Diagram 4: Multizone System With Circulators And Domestic Hot Water Priority

35