Ar822-ii, Appendix a - boiler piping and wiring 37, Dhw circ – Dunkirk Q95M-200 Modulating Condensing Boiler User Manual

Page 37: L1 & l2 to arm l & n on priority zone, Indirect hot water heater aquastat or thermostat

Advertising
background image

120V AC

L2 N

L1 (HOT)

BOILER CIRC (WILL RUN FOR ALL CH

AND DHW CALLS FOR HEAT)

ELEC

TR

ONIC FUSE

VAC

CIR

CUIT ON

L2

120

NO

4

NC

4

6 TO 7 INCH LBS

TORQUE TERMINAL

SCREWS

AR822-TT

TT

T

T

R W

24V

C

AR822-II

5 6

NO

6

NC

Boiler Control Panel

DHW C1

DHW C2

CH C2

L2

ARM-4P

L1

CH C1

PRIORITY

CONTROL WITH

AIR SENSOR

OUTDOOR

A2

CH T2

DHW T1

DHW T2

A1

CH T1

DHW CIRC

NORMALY OPEN

115 V COIL / ISOLATION RELAY

L

CIRC 2

SWITCH

ISOLATED

X X

ZR

ZC

L

1

N

ZONE 1

CIRC 4

CIRC 3

ZONE 4

ZONE 4

ZONE 3

ZONE 2

N

2

L

N

3

L

ZONE 3

ZONE 2

120 VAC

4

N

L

N

PRIORITY ON

INDIRECT HOT WATER HEATER

AQUASTAT OR THERMOSTAT

W

T-STAT

DATA PORT

X-X

ZR-ZC

W

T

PRIORITY

T

1

ZONE

T

R

ZONE 4

THERMOSTATS

ZONE 3

T

ZONE 2

2

W

T

R

3

T

T

W

R

TO EXTRA

ZONE MODULE

T

4

R

@ 1VA

24 VAC

COMMON

T-STAT

T-STAT

15 VA

2.7K

SILKSCREEN

1.2K

L1 & L2 TO ARM L &

N ON PRIORITY ZONE

ELEC

TR

ONIC FUSE

VAC

CIR

CUIT ON

120

L2

NO

4

NC

4

SCREWS

TORQUE TERMINAL

6 TO 7 INCH LBS

AR822-TT

TT

T

T
R W

24V

C 5 6

NO

6

NC

TERMINAL 5 & 6 N.O.

TO DHW T1 & DHW T2

NOTE: IN PLACE OF 115

VOLT ISOLATION RELAY,

OPTIONAL CONTROL

ARGO AR822II

Wiring Diagram 5 : Primary/Secondary Wiring With Circulators And Domestic Hot Water

APPENDIX A - BOILER PIPING AND WIRING

37