10.1 Codes

Electrically bond boiler to ground in accordance with

requirements of authority having jurisdiction. In absence

of such requirements, Refer to:

• USA - National Electrical Code, ANSI/NFPA 70.
• Canada - Canadian Electrical Code, Part I, CSA C22.1:

Safety Standard for Electrical Installations.

10.2 Line Voltage Connections
1.

Connect 120 VAC power wiring to line voltage terminal

strip on boiler control panel.

2.

Provide and install fused disconnect or service switch

(15 amp recommended) as required by code.

3.

Boiler circulator is shipped loose. Wire boiler circulator

as shown in wire diagram label on boiler side panel.

(CH L1, CH L2) CH = Central Heat

4.

When connecting DHW circulator, connect wiring to line

voltage terminal strip on boiler control panel. (DHW L1,

DHW L2) DHW = Domestic Hot Water

5.

Route all wires and conduits to openings in right jacket
panel.

10.3 Line Voltage Monitor

• Boiler is factory equipped with line voltage monitor that

continuously monitors incoming voltage for errors.

• When incoming line voltage is greater than 12% or less

than 8% of nominal voltage monitor will flash indicating

fault.

• 6 Seconds after line voltage is back within acceptable

range green light will illuminate on monitor and boiler will

restart. Line voltage monitor is factory set at 115 VAC.

It is important that monitor be set to voltage present at

installation site by following these directions:

1.

Using multimeter, locate wall outlet nearest to boiler

and determine line voltage present on site.

2.

Disconnect power to boiler.

3.

Remove boiler cover.

4.

Locate line voltage monitor mounted to display panel.

5.

Remove line monitor protective cover.

6.

Using small screwdriver turn left dial until arrow points

at input voltage measured during step 1.

7.

Set right dial at 0.1 minute, this is factory setting.

8.

Reinstall line monitor protective cover.

9.

Replace boiler cover and re-connect power to unit.

WARNING

Electrical shock hazard. Turn OFF electrical power

supply at service panel before making electrical

connections. Failure to do so could result in death or

serious injury.

!

10 - ELECTRICAL WIRING

NOTICE

Use only N.E.C. Class 1 wiring. If replacing original

boiler wiring, use only type 105°C wire or equivalent.

See Piping and Wiring Appendix for wiring

and piping diagrams.

Figure 11 - Line Voltage Monitor

10.4 Low Voltage Connections

1.

Connect low voltage wiring to low voltage terminal strip

as shown in boiler wiring diagram.

2.

Route all low voltage wires through opening on right
jacket panel. Use shielded cable.

L1 L2

19