Warning – Dunkirk Q95M-200 Modulating Condensing Boiler User Manual

Page 22

Advertising
background image

• High limit control is mounted in ½” NPT control well

and ¾” X ½” bushing on top of front boiler section at

hot water outlet.

• High limit control is tied in with boiler control and is

factory set at 180°F (82°C) water temperature.

• High limit setpoint is field adjustable and may be set

anywhere between 100°F (38°C) and 180°F (82°C),

with maximum high limit setpoint not exceeding 180°F

(82°C). Field high limit setpoint adjustment for each

installation depends on heating system requirements.

• High limit control automatically resets when boiler water

temperature decreases below high limit setpoint value

by differential setpoint value. Adjustable differential from

5°F (3°C) to 30°F (17°C).

• Boiler operating temperature (temperature curve) is

calculated and set in boiler control parameters.

11.13 Casting Temperature Safety Switch

• Casting temperature safety switch, 230°F (110°C)

setpoint, shuts off power to boiler control in event of

boiler lack of or loss of water.

• Casting temperature safety switch is installed on top of

aluminum boiler section behind supply piping.

• Failure code is displayed on digital readout. Fault

requires manual reset of casting temperature safety

switch to restart boiler. Press reset on user interface

panel also.

• Verify boiler is properly filled with water and no air is

trapped in top of casting (check cap on Cam Vent at

heat exchanger) before resetting.

WARNING

Burn and scald hazard. Never run cold water into a

hot, empty boiler. Failure to follow these instructions

could result in death or serious injury

!

11.14

Circulator Pump

• Circulating pump moves water through closed loop

supply and return piping systems, terminal heating

equipment (finned tube radiators, etc.) and back

through boiler for reheating.

• Properly size circulator pump to overcome frictional

losses (usually measured in feet of water, also referred

to as “pump head loss”) of supply and return piping

systems and boiler to provide required hot water flow

rates.

• Circulator pump is furnished in carton within boiler

cabinet.

• Locate circulator(s) on downstream (“pumping away”)

side of expansion tank.

11.15 Blocked Vent Safety Assembly

Blocked vent safety assembly incorporates two pressure

switches designed to discontinue operation of boiler if there

is a problem with blower or venting system.
The normally open switch closes upon initiation of blower

and functions as air proving switch.
The normally closed switch opens if there is a blockage in

combustion air intake or exhaust vent pipes.

11.16 Drain Valve

Manual drain valve drains water in heating system,

including boiler, hot water supply and return piping systems

installed above drain valve.
Drain valve is installed in return piping at bottom front of

boiler section. Any piping installed below elevation of drain

valve requires additional drain valves to be installed at low

points in piping system in order to drain entire system.

WARNING

Burn and scald hazard. Safety relief valve could

discharge steam or hot water during operation.

Install discharge piping per these instructions.

!

11.17 Safety Relief Valve

• Each boiler must have a properly sized and installed

American Society of Mechanical Engineers (ASME) rated

safety relief valve.

• Furnished safety relief valve automatically opens at 30

psig pressure to relieve strain on boiler and heating

system from increasing pressure.

• Pipe Safety relief valve discharge with same size pipe

as valve discharge opening to open drain, tub or sink,

or other suitable drainage point not subject to freezing.

11.18 External Condensate Pump (optional)

For installations where there is no floor drain or other

appropriate drainage receptacle available to receive

condensate from boiler, external float activated condensate

pump with integral sump is required. Condensate pump can

be piped to remote tie in point to sanitary sewer system.

For this application, boiler must be installed so that proper

pitch of piping to external condensate reservoir (sump) can

be accomplished. Use wood frame or concrete blocks to

raise boiler as required for proper installation.

11.19 Concentric Vent/Air Intake Termination

(Optional)

Optional concentric vent/air intake termination utilizes

single opening per each appliance through wall or roof of

structure.

11 - CONTROLS AND ACCESSORIES

22