8 - COMBUSTION AIR AND VENT PIPE

Combustion

Air

Vent

1" (26mm)

Maximum

1" (26mm)

Maximum

Roof Overhang

* See Note

Below

Vent

Combustion

Air

36"(915mm) Minimum

Maintain 12"(300mm)

clearance above highest

anticipated snow level or

grade

12" (300mm) Minimum

*Must be less than 4" (102mm) or greater than

24"(610mm) Horizontal distance between end bells of each

air intake to prevent flue gas recirculation.

Figure 6 -Roof Vent / Intake Terminations

Figure 7 - Concentric Vent Terminations

3” MINIMUM

SEPARATION