Water Treatment And Freeze Protection - See

Appendix B

12.1 Filling Boiler With Water And Purging Air

1.

Systems With Diaphragm Type Expansion Tanks

A. Close all zone service valves on supply and return

piping. Open feed valve and fill boiler with water.

Verify air vent is open. Hold relief valve open until

water runs air free for five seconds to rapidly bleed

air from boiler, then let relief valve snap shut.

B. Open zone service valve on supply pipe for first

zone. Open purge valve on first zone. Feed water

will fill zone, pushing air out purge valve. Close

purge valve when water runs air free. Close zone

service valve.

C. Repeat step 2 for all remaining zones.
D. Open all service valves. Any air remaining trapped

in return lines between service valves and boiler

will be pushed towards air vent when boiler is

placed in operation.

E. Inspect piping system and repair any leaks

immediately.

12 - BOILER STARTUP

2.

Systems With Conventional Closed Type Expansion

Tanks

A. Close all zone service valves on supply and return

piping and close expansion tank service valve.

Drain expansion tank. Open feed valve and fill

boiler with water. Hold relief valve open until water

runs air free for five seconds to rapidly bleed air

from boiler, then let relief valve snap shut.

B. Open zone service valve on supply pipe for first

zone. Open purge valve on first zone. Feed water

will fill zone, pushing air out purge valve. Close

purge valve when water runs air free. Close zone

service valve.

C. Repeat step 2 for all remaining zones.
D. Open expansion tank service valve and tank

vent. Fill tank to proper level and close tank vent.

Remove handle from expansion tank service valve

so it is not accidentally closed.

E. Open all service valves. Any air remaining trapped

in return lines between service valves and boiler

will be pushed towards expansion tank when boiler

is placed in operation.

F. Inspect piping system. Repair any leaks immediately.

NOTICE

Do not use stop leak compounds. Repair leaks in

threaded connections of aluminum boiler sections.

Aluminum threads do not seal themselves.

23