THREE PHASE STANDARD CIRWATT B METER

CIRWATT B THREE PHASE INSTRUCTION MANUAL

27 / 53

1.31.3.- Seals


The CIRWATT Type B meter can be protected using the following seals:




















1.32.- Measurement validation criteria

Energy, maximeter and excesses registers will be invalidated following the occurrence of a
series of events that implies that their values are false. In the specific case of the load curve
registers, there exists an invalid bit (IV) which indicates that that register is no longer valid. The
events that lead to this invalidity of the measurements are described below.

1.32.1.- Time synchronization with drift > T1 = 30 seconds

The quarter-of-an-hour period in which the synchronization takes place will be ignored for the power
calculation.

1.32.2.- Time synchronization with drift >10 minutes

The measurement is invalidated, i.e. flag IV = 1.

1.32.3.- Communication failure between meter and analyzer


If the communications failure coincides with the quarter-of-an-hour period change, and its
duration is longer than 30 seconds, the affected periods will be ignored for the power
calculation.

Manufacturer's seal
(underneath

the

wire

cover)

Wire cover seal

Button seal

Transformer ratio seal