THREE PHASE STANDARD CIRWATT B METER

CIRWATT B THREE PHASE INSTRUCTION MANUAL

39 / 53

Screen L4 (INFORMATION)


This is the screen that gives access to the information not related to the billing values of the
contracts.


L4

Infor



It gives access to the other, dependent MENU screens, shown below:

Screens

Description

Comments

L40

Indic

OPERATING INDICATORS

For checking that all of the fundamental aspects of the equipment are
working correctly, during installation or during subsequent in situ
checks.

L41

Cont.P

CONTRACTED POWER

Used to indicate the values of the contracted powers. Only applies to
power excesses in Contract 1.

L42

tr.rAt

TRANSFORMER RATIOS

Displays information about the transformer ratios.

L43

C.UAL

CURRENT VALUES

Displays information about the current values of power, maximum,
totalizers, and the power of the last integration period (15 minutes by
default).

L44

I.UAL

INSTANT VALUES

Displays information about the instant values of different electrical
factors.

L45

Co

COMMUNICATIONS

Displays information about the different communications port
parameters.

L46

Ident

IDENTIFIERS

Displays information about the different device IDs, including those
relating to the IEC870-5-102 protocol.

L47

OUtput

OUTPUT CONSTANTS

Displays information about the output impulse values.

L48

HoUr L

CLOCK CHANGES

Displays information about daylight saving clock change dates.

return

BACK

Returns to the previous screen.

Screen L40 (INFORMATION: INDICATORS)


This is the screen that shows the information about the operating indicators. It is used to check
that all of the fundamental aspects of the equipment are working correctly, during installation
or during subsequent in situ checks.

Display

OBIS

Description

L40

Indic

0.13.38

e.g. 1

ACTIVE QUADRANT: Indicates the direction of the active and reactive energy or
quadrant (1, 2, 3 or 4).

0.12.38

e.g. 123

VOLTAGE PRESENCE: Indicates the presence of voltage in each phase (123 if all
have voltage, blank if there is no voltage present)

0.11.38

e.g. 120

CURRENT DIRECTION: Indicates the input (+) or output (-) direction in each phase
(111 if they are inputs, 222 if they are outputs, 000 if they do not exist).

0.18.12

e.g. 633

ACTIVE TARIFF OF EACH CONTRACT: Indicates the active tariff, at the moment of
reading, of each contract (contract 1, contract 2, contract 3) (values ranging from 1 to
6 for each contract).

0.96.2.4

e.g. 0

PARAMETERISATION MODE: Indicates whether or not the parameterisation mode is
enabled (0 disabled, 1 enabled).

0.96.5.0

e.g.

C

ALARMS: Indicates the alarms defined in section 1.7. The data field will display the
letters

Cnb, which will appear depending on the nature of the alarm.