Metrology, Measured magnitudes, Nominal, maximum and minimum operating conditions – CIRCUTOR CIRWATT-B410T Series User Manual

Page 9: Electrical parameters, Electrical parameters reference voltage (u, O maximum: 120% u

Advertising
background image

THREE PHASE STANDARD CIRWATT B METER

CIRWATT B THREE PHASE INSTRUCTION MANUAL

9 / 53

(1) Option only available for direct meters with three phase internal relay.

Example: The code 410UD1A90B10 represents a Type B Standard meter, Class B for active energy (Class 1) and Class 2 for reactive
energy, with asymmetric connection, 50Hz, 4 quadrants; with supply/ voltage between 3 x 127(230)V and 3 x 230(400)V and 10(100) A , with
RS232 and RS485 communications; without expansion module or extra features.

1.3.- Metrology

The metrological characteristics for the Cirwatt Three-Phase Type B (TBT) are:

The current sensor is of the current transformer type.

Current ranges:

Active Class B (1)

Indirect / semi-indirect connection version

I

tr

0,250

I

st

0,010

I

min

0,050

I

n

/ I

ref

5,000

I

max

10,000

Direct connection version

I

tr

1,000

I

st

0,040

I

min

0,500

I

n

/ I

ref

10,000

I

max

100,000

1.4.- Measured magnitudes

The meter is able to measure the following variables:

Imported and exported active and reactive energy in the four quadrants.

Active and Reactive Power.

Instantaneous current and voltage.

Cos .

1.5.- Nominal, maximum and minimum operating conditions

1.5.1.- Electrical parameters

Reference voltage (U

ref

):

3x57/100V to 3x230/400V (depending on version)

Operating voltages

o minimum:

80% U

ref

o maximum:

120% U

ref

Advertising