Supply interruptions – CIRCUTOR CIRWATT-B410T Series User Manual

Page 31

Advertising
background image

THREE PHASE STANDARD CIRWATT B METER

CIRWATT B THREE PHASE INSTRUCTION MANUAL

31 / 53

E) Minimum duration out-voltage

Is the minimum time where the voltage has to be out of limits (continuously) to create a
voltage event. If this value is set to zero, the meter will not register this kind of event.

2.9.2.- Supply interruptions


To calculate the variable when the voltage is out of limits, 3 variables must be programmed on
the meter: Nominal voltage, Threshold separation, Minimum duration out-voltage.

The meter will separate the incidences in curse (still actives) from the closed incidences
(finished). In each event the following parameters will be saved: affected phase, initial event
date and hour and final date and hour. With a resolution of a second.

A) Nominal voltage and Threshold separation

Those parameters are defined on the previous points. The values under this limits will be
voltage interruptions.

B) .Minimum duration out-voltage

Is the minimum time where the voltage has to be out of limits (continuously) to create a
voltage event (interruption). If this value is set to zero, the meter will not register this kind of
event. If this value is set to zero, the meter will not register this kind of event.