THREE PHASE STANDARD CIRWATT B METER

CIRWATT B THREE PHASE INSTRUCTION MANUAL

40 / 53

Screen L41 (INFORMATION: CONTRACT PARAMETERS)


This is the screen that shows the information about the contracted power of contract 1. Only
applies to power excesses in Contract 1. It is a DATA screen.

Display

OBIS

Description

L41

Cont.P

1.135.1

CONTRACTED POWER: Indicates the values, in kW to 2 decimal places, of the
contracted powers that will be used for calculating the excesses.

1.135.x where x = tariff (period)

1.135.2
1.135.3
1.135.4

Screen L42 (INFORMATION: TRANSFORMER RATIOS)


This is the screen that shows the information about the transformer ratios. It is a DATA screen.

Display

OBIS

Description

L42

tr.rAt

0.04.2

CURRENT RATIO PRIMARY: Displays the value of the primary of the current ratio, to 1
decimal place.

0.04.5

CURRENT RATIO SECONDARY: Displays the value of the secondary of the current
ratio, to 1 decimal place.

0.04.3

VOLTAGE RATIO PRIMARY: Displays the value of the primary of the voltage ratio, to 1
decimal place (compound voltage).

0.04.6

VOLTAGE RATIO SECONDARY: Displays the value of the secondary of the voltage
ratio, to 1 decimal place (compound voltage).

Screen L43 (INFORMATION: CURRENT VALUES)


This is the screen that shows information about the current values of power, maximum,
totalizers, and the power of the last integration period (15 minutes by default). It is a DATA
screen.

Display

OBIS

Description

L43

C.UAL

0.18.0

TOTALIZER A+: Displays the value of the current totalizer of Active Energy taken from
the network.

0.28.0

TOTALIZER A-: Displays the value of the current totalizer of Active Energy injected to
the network.

0.58.0

TOTALIZER R1: Displays the value of the current totalizer of Reactive Energy from
quadrant 1.

0.68.0

TOTALIZER R2: Displays the value of the current totalizer of Reactive Energy from
quadrant 2.

0.78.0

TOTALIZER R3: Displays the value of the current totalizer of Reactive Energy from
quadrant 3.

0.88.0

TOTALIZER R4: Displays the value of the current totalizer of Reactive Energy from
quadrant 4.

0.14.0

CURRENT POWER INPUT: Displays the value of the average input power being
integrated during the current integration period.

0.24.0

CURRENT POWER OUTPUT: Displays the value of the average output power being
integrated during the current integration period.

0.15.0

LAST PERIOD POWER INPUT: Displays the value of the average input power that has
been integrated during the last integration period.

0.25.0

LAST PERIOD POWER OUTPUT: Displays the value of the average output power that
has been integrated during the last integration period.