THREE PHASE STANDARD CIRWATT B METER

CIRWATT B THREE PHASE INSTRUCTION MANUAL

41 / 53

Screen L44 (INFORMATION: INSTANT VALUES)


This screen displays information about the instant values of different electrical factors. Since
said data does not correspond to any specific contract, but is instead data which is relevant to
all of them, field B takes the value 0.

Display

OBIS

Description

L44

I.UAL

0.327.0

VOLTAGE PER PHASE: These display the instant voltage values for each phase.

0.527.0
0.727.0
0.317.0

CURRENT PER PHASE: These display the instant current values for each phase.

0.517.0
0.717.0
0.337.0

COS Φ PER PHASE: These display the instant cos Φ values for each phase.

0.537.0
0.737.0

0.17.0

INSTANT ACTIVE POWER: Displays the total instant Active Power value for the three
phases with their symbol.

0.37.0

INSTANT REACTIVE POWER: Displays the total instant Reactive Power value for the
three phases with their symbol.

0.137.0

AVERAGE POWER FACTOR: Displays the average instant Power Factor value for all
the phases.

Screen L45 (INFORMATION: COMMUNICATIONS)


This screen displays information about the different communications port parameters. Since
said data does not correspond to any specific contract, but is instead data which is relevant to
all of them, field B takes the value 0.

Display

OBIS

Description

L45

CoM

0.00.0

OPTICAL SERIAL PORT CONFIGURATION: 000000n (009600 speed, n parity).

0.00.1

ELECTRICAL SERIAL PORT 1 CONFIGURATION: 000000n (009600 speed, n parity).

0.00.2

ELECTRICAL SERIAL PORT 2 CONFIGURATION: 000000n (009600 speed, n parity).

0.00.3

ELECTRICAL SERIAL PORT 1 MODEM STARTUP MODE: The data corresponding to
the protocol's ASDU 142 will be displayed.

Screen L46 (INFORMATION: IDENTIFIERS)


This screen displays information about the different device IDs, including those relating to the
IEC-870-5-102protocol. Since said data does not correspond to any specific contract, but is
instead data which is relevant to all of them, field B takes the value 0.

Display

OBIS

Description

L46

Ident

0.00.5

LINK ADDRESS

0.00.6

MEASURING POINT ADDRESS

0.00.7

DATA OF THE COMMUNICATIONS PROTOCOL VERSION: (DD-MM-YY), showing the
data corresponding to the protocol's ASDU 142.

0.02.0

DEVICE FIRMWARE VERSION: showing the data corresponding to the protocol's ASDU
142.

0.08.4

INTEGRATION PERIOD OF THE FIRST LOAD CURVE: indicates the integration period,
in minutes; 60 minutes by default.

0.08.5

INTEGRATION PERIOD OF THE SECOND LOAD CURVE: indicates the integration
period of the second load curve, in minutes; 15 minutes by default.