When the 440 V capacitor power reference is used for a 400 V grid voltage, the following table is used:

CT Ratio

(I

p

/I

s

)

Power in kvar of the smallest stage, in kvar, at 440 V

2.5

5.00

7.5

10.0

12.5

15.0

20.0

25.0

30.0

40.0

50.0

60.0

75.0

80.0

150/5

0.09 0.18 0.27 0.36 0.45

0.54 0.72 0.90

200/5

0.07 0.14 0.20 0.27 0.34

0.41 0.54 0.68 0.81

250/5

0.05 0.11 0.16 0.22 0.27

0.33 0.43 0.54 0.65 0.87

300/5

0.05 0.09 0.14 0.18 0.23

0.27 0.36 0.45 0.54 0.72 0.90

400/5

0.07 0.10 0.14 0.17

0.20 0.27 0.34 0.41 0.54 0.68 0.81

500/5

0.05 0.08 0.11 0.14

0.16 0.22 0.27 0.33 0.43 0.54 0.65 0.81 0.87

600/5

0.05 0.07 0.09 0.11

0.14 0.18 0.23 0.27 0.36 0.45 0.54 0.68 0.72

800/5

0.05 0.07 0.08

0.10 0.14 0.17 0.20 0.27 0.34 0.41 0.51 0.54

1000/5

0.04 0.05 0.07

0.08 0.11 0.14 0.16 0.22 0.27 0.33 0.41 0.43

1500/5

0.04 0.05

0.05 0.07 0.09 0.11 0.14 0.18 0.22 0.27 0.29

2000/5

0.04 0.05 0.07 0.08 0.11 0.14 0.16 0.20 0.22

2500/5

0.04 0.05 0.07 0.09 0.11 0.13 0.16 0.17

3000/5

0.04 0.05 0.05 0.07 0.09 0.11 0.14 0.14

4000/5

0.04 0.05 0.07 0.08 0.10 0.11



IMPORTANT!:

When the C/K adjustment is configured under the real values, there will be a series of continuous
connections and disconnections with minor load variations. (The system performs more operations than
those actually needed).

When the C/K adjustment is configured as "high" (10%), the regulator will need a higher reactive power
demand to perform the switching operations and, therefore, perform fewer operations.


Calculation of the C/K Factor

In the case of values that have not been included in the table, the C/K factor can be calculated as follows:

The reactive power of the smallest capacitor Q and the grid voltage U must be known. The current of this

capacitor will be then calculated as

V

.

Q

C

I

3

=

The transformation ratio of the current transformer must also be known. This is the K factor:

sec

I

prim

I

K

/

=

where: Iprim is the nominal current of the transformer's primary (for example, it would be 250A in a 250/5)

Isec is the transformer's secondary current. Usually 5 A.

Therefore, the C/K factor will be:

V

K

Q

K

I

K

C

C

=

=

3

/


For example: In a 400V unit, the smallest capacitor is 60 kVAr with a current transformer with a 500/5 ratio.
The calculation is as follows:


K factor

100

5

/

500

=

=

K

Current of the smallest capacitor

A

I

C

6

,

86

400

3

1000

60

=

=

C/K value

866

,

0

100

6

,

86

/

=

=

=

K

Ic

K

C


When the 60kvar power is referenced to 440 V, it must be multiplied by Ugrid^2/440^2, so that the previous
example would be:

A

I

C

6

.

71

2

^

440

3

400

*

1000

60

=

=

72

,

0

/

=

K

C