Getting Started

Emotron AB 01-2120-01r2

4.4

Auto set performed at snoring – pumping a
mix of air and water

1. Set the pump system control equipment to the off position or “0”, and

switch on the supply voltage to the Emotron DCM.

2. Step to window 13 with the

button and press

so that the line is

shown at the bottom of the display (_). Then press

to confirm the set-

ting. The Emotron DCM is now ready for Auto set at snoring.

3. Set the pump system control equipment to the on position, “1” or Auto to

start the pump. If necessary, press

to start the pump.

4. Run the pump until it starts to snore.

5. Press

until “SEt” is shown on the display. The stop level is now set, thus

stopping the pump when snoring.

The stop function is now initiated and the Emotron DCM controls the pump.
Adjustments can be made according to Section 6.2, page 30. See also Sections
6.3 and 6.4.

Fig. 3

Auto set performed at snoring

NEXT

ENTER

ENTER

SET

AUTO

SET

AUTO

Power pump

Auto set is pressed

Normal pump load power (window 04)

Stop level (window 11)

Power level
when snoring

Time

Snore margin (window 12)