Emotron AB 01-2120-01r2

Single-Pump System Installation

33

pause time (window 22). The parameters can be adjusted to achieve desired
magnitudes of pause times, start level and number of starts per hour. See Fig.
11, page 23, an
d 14, page 32.

The level setting in window 21 is set for shorter or longer pumping and pause
cycles. Higher values increase the calculated pause time and the amount of accu-
mulated water.

The level setting is best adjusted after a few pumping cycles in order to adjust
the pause time, and hence the start level in the pit. See schematic pump cycle
example in Fig. 11 and 14.

Maximum pause time for the pump is set in window 22. The calculated pause
time will be limited to this value. In some applications the inflow may increase
rapidly during a pause. To prevent overflow in these situations the maximum
pause time can be set in accordance with the circumstances.

6.5

Returning to the default settings

1. To return to the default settings go to window 99.

2. If any value differs from the default values (see Table 8). “Usr” (set by the

user) is displayed in the window.

3. Press

to return to the default settings. “dEF” (default setting) is shown

in the window. Confirm by pressing

.

NOTE: Also, windows 6, 7 and 8 are set to 0.