3 returning to the default settings, Returning to the default settings – Crompton Controls DCM User Manual

Page 41

Advertising
background image

40

Dual-Pump System Installation

Emotron AB 01-2120-01r2

17. Change the level setting in window 21 on the MASTER DCM between 1 -

10 for shorter or longer pump cycles and level in the pit. A low value gives
shorter pump cycles and lower level in the pit, see Fig. 11, page 23 and 14,
page 32.

18. It is possible to avoid unintentional changes to set parameters. Set window

09 to 369 in each DCM and confirm with

. A padlock is shown in the

window. If the value 369 is re-entered in window 09 and confirmed by

the settings are unlocked.

7.3

Returning to the default settings

1. To return to the default settings go to window 99.

2. If any value differs from the default values (see Table 8), “Usr” (set by the

user) is displayed in the window.

3. Press

to return to the default settings. “dEF” (default setting) is shown

in the window. Confirm by pressing

.

NOTE: Also, windows 6, 7 and 8 are set to 0.

ENTER

ENTER

ENTER

Advertising