Emotron AB 01-2120-01r2

Installation

25

5.4

Connection terminals

There are 13 connection terminals on the front panel of the Emotron DCM.

Table 5

Labelling and functions of connection terminals.

Terminal

Label

Function

1

S1

Current transformer input (CTM xxx), blue wire.

2

S2

Current transformer input (CTM xxx), brown wire.

3

DIG

Digital input for closing contact. High-level switch or
external reset/Auto set. In dual-pump applications
terminal 3 is also used for communication between
the two DCMs.

4

SGND

Signal ground for terminals 3 and 5.

5

TEMP

Input for motor thermistor (PTC), thermal contact, and/
or any voltage-free opening contact or motor protec-
tion relay.

6

ALARM

Alarm relay output. (The DCM MASTER uses this
terminal in series with the high-level switch.

7

C

Common input for alarm and pump relay.

8

PUMP

Operation of relay pump motor (control signals for start
and stop equipment).

9

L1

Supply voltage L1.

10

(not used)

11

L2

Supply voltage L2.

12

(not used)

13

L3

Supply voltage L3.