Fig. 11 Pump cycle example with different level settings in window 21

700

600

500

400

300

200

100

0

V

olume

in the

pit

in litres

Example 1

Inflow 300 litr es/min
Pump capacity 600 litres/min

Window 21 is set to 1

Time

700

600

500

400

300

200

100

0

V

olume

i n

the

p

i t

i n

l

i tres

Example 2

Inflow 100 litr es/min
Pump capacity 600 litr es/min

Window 21 is set to 1

Time

1400

1600

1200

800

600

400

200

0

V

olume

i n

the

p

i t

i n

l

i tres

Example 3

Inflow 300 litr es/min
Pump capacity 600 litr es/min

Window 21 is set to 2,3

Time

1000

The volume in the pit at
pump start after pause
time is equal to pump
capacity (litres/min) mul-
tiplied by level setting
(window 21).

Examples 1 and 2:
Pump capacity
600 (litres/min) x 1
(Value in window 21) =
600 litres in the pit when
the pump starts to pump.

Example 3:
Pump capacity 600
(litres/min) x 2.3 (value in
window 21) = 1380 litres
in the pit when the pump
starts to pump.