Crompton Controls DCM User Manual

Page 18

Advertising
background image

Emotron AB 01-2120-01r2

Installation

17

For larger motors (rated current > 100 A), use two current transformers - one
outer, standard transformer, and one CTM010 with two windings. Table 2
shows the choice of transformers (standard + CTM010) and number of wind-
ings for currents exceeding 100 A.

The following examples illustrate the choice of current transformer(s):

Example A. Pump motor has a rated current of 6.9 A. According to Table 1,
choose CTM010 with one (1) winding.

Example B. Pump motor has a rated current of 108 A. According to Table 2,
choose a standard current transformer 150:5 with one (1) winding and a
CTM010 with two (2) windings.

In order to ensure accurate calibration of the Emotron DCM, it is essential that
you use the correct CTM (and, additionally, a standard current transformer)
and apply the exact number of wirings in accordance with the tables above.

Table 2

Table for selection of current transformers for motors with a rated current
greater than 100 A

Rated motor current

Current transformers

Number of windings

101 to 150 A

150:5 +

CTM010

1 +

2

151 to 250 A

250:5 + CTM010

1 +

2

251 to 500 A

500:5 + CTM010

1 +

2

501 to 999 A

1000:5 + CTM010

1

+ 2

NOTE: The current transformer must be linked to the phase connected to
terminal 9 (L1).