Emotron AB 01-2120-01r2

Window Parameters

55

21

Pit volume and level setting,
see Fig. 11, page 23 and Fig.
14, page 32. See
also note on
page 22. NOTE! The window is
not shown when the DCM is
SLAVE.

1.0 to 10.0

1.0

22

Maximum pause time.
NOTE! The window is not
shown when the DCM is
SLAVE. Symbol

.

0 to 900 s
15 - 720
min.

600 s

23

Start-up delay.
Symbol .

1 to 170 s

5 s

24

Stop delay.
Symbol .

1 to 90 s

2 s

31

High temperature on pump
motor or motor protection
alarm, terminal 5 (on). Turn off
(OFF).

on / OFF

OFF

32

Latched alarm, terminal 5 (on).
Alarm not latched (OFF). Can
only be used when window 31
is (on).

on / OFF

OFF

41

Phase asymmetry permitted.

OFF/ 5 to
50%

10%

42

Phase asymmetry latched
alarm (on). Phase asymmetry
alarm not latched. (OFF) Can
be used when window 41 is set
between 5-50%.

on / OFF

OFF

Table 8

Window parameters and defaults

Window

Function

Value

Default

Custom

setting

Master Slave