Crompton Controls DCM User Manual

Page 57

Advertising
background image

56

Window Parameters

Emotron AB 01-2120-01r2

51

Alarm relay (terminal 6
ALARM).
NC: normally closed,
NO: normally open.
The window isn’t shown when
DCM is MASTER

NC/NO

NO

52

Operating relay to control the
pump motors contactor
(terminal 8 PUMP).
NC: Relay contact is closed
when pump is pumping.
NO: Relay contact is open
when pump is pumping.

NC/NO

NC

53

Digital input for closing
contact:
1 High-level switch
2 External reset
3 External Auto set (not used
in dual-pump system).

1

61

Measured current on the
terminals S1 and S2.

0-70 mA

71

Desired DCM function:
1 Single-pump system
2 Dual-pump system MASTER
3 Dual-pump system SLAVE.

1, 2, 3

1

72

Pump alternating:
(on) Alternate by each pump
cycle (OFF) The SLAVE DCM
only starts when the DCM
MASTER indicates a fault code.
NOTE! The window is not
shown when the DCM is
SLAVE.

on/OFF

OFF

Table 8

Window parameters and defaults

Window

Function

Value

Default

Custom

setting

Master Slave