Installation

(For Qualified Installers Only)

© Travis Industries

4141230

100-01341

Venting the Pellet Insert

INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER.
DO NOT CONNECT THE PELLET VENT TO A VENT SERVING ANY OTHER APPLIANCE OR

INSERT.

DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
USE AN APPROVED WALL THIMBLE WHEN PASSING THE VENT THROUGH WALLS AND

A CEILING SUPPORT/FIRE-STOP SPACER WHEN PASSING THE VENT THROUGH
CEILINGS (MAKE SURE TO MAINTAIN CLEARANCE TO ANY COMBUSTIBLES).

Maximum Venting Distance:

Maximum venting height is 35' (maximum horizontal offset is 10')

Use no more than 180° of elbows (two 90° elbows, or two 45° & one 90° elbow, etc.).

Pellet Vent Type

Must be Type "L" vent and/or Type "L" chimney liner.

3” diameter vent may be used if vent is 20’ or less.

4" diameter vent is required if vent height is over 20’.

Installing the Pellet Vent

Pellet vent connections must be sealed
airtight with 500° F. RTV silicone and
screwed together with at least three
sheet metal screws.

Pellet Vent Termination

Termination must be a minimum 6" above the top of the chimney (NOTE: the chimney must meet
local codes for height above the roof or other obstructions).

Must have an approved cap (to prevent water from entering).

Must not be located where it will become plugged by snow or other material.

 This fireplace insert must be installed with a continuous chimney liner of 3” or 4” diameter

extending from the fireplace insert to the top of the chimney. The chimney liner must conform to
the Class 3 requirements of CAN/ULC-S636, Standard for Lining Systems for Existing Masonry or
Factory-Built Chimneys and Vents, or CAN/ULC-S640, Standard for Lining Systems for New
Masonry Chimneys.

Seal each vent section (including
adapters, elbows, etc...) by
injecting a liberal amount of 500°
F. RTV silicone into the gap
between sections.

500° F. RTV

Silicone

The exhaust quick-

connect can be

removed to allow for
installation and

cleaning.