State Transitions

The network management messages have a very simple structure: CAN identifier 0, with two bytes of data con-
tent. The first data byte contains what is known as the command specifier (cs), and the second data byte con-
tains the node address, the node address 0 applying to all nodes (broadcast).

11 bit identifier

2 byte of user data

0x00

cs Node-ID

The following table gives an overview of all the CANopen state transitions and the associated commands
(command specifier in the NMT master telegram):

Status
transition

Command
Specifier cs

Explanation

(1)

-

The initialisation state is reached automatically at power-up

(2)

-

After initialisation the pre-operational state is reached automatically - this
involves sending the boot-up message.

(3), (6)

cs = 1 = 0x01

Start_Remote_Node.
Starts the module, enables outputs, starts transmission of PDOs.

(4), (7)

cs = 128 = 0x80

Enter_Pre-Operational. Stops PDO transmission, SDO still active.

(5), (8)

cs = 2 = 0x02

Stop_Remote_Node.
Outputs go into the fault state, SDO and PDO switched off.

(9), (10),
(11)

cs = 129 = 0x81

Reset_Node. Carries out a reset. All objects are reset to their power-on
defaults.

(12), (13),
(14)

cs = 130 = 0x82

Reset_Communication. Carries out a reset of the communication functions.
Objects 0x1000 - 0x1FFF are reset to their power-on defaults.

Example 1

The following telegram puts all the modules in the network into the error state (outputs in a safe state):

11 bit identifier

2 byte of user data

0x00

0x02

0x00

Example 2

The following telegram resets node 17:

11 bit identifier

2 byte of user data

0x00

0x81

0x11

Boot-up message

After the initialisation phase and the self test, the bus coupler sends the boot-up message, a CAN message
with one data byte (0) and the identifier of the guarding or heartbeat message: CAN-ID = 0x700 + Node-ID. In
this way temporary failure of a module during operation (e.g. due to a voltage interruption), or a module that is
switched on at a later stage, can be reliably detected, even without Node Guarding. The sender can be deter-
mined from the message identifier (see default identifier distribution).

It is also possible, with the aid of the boot-up message, to recognise the nodes present in the network at start-
up with a simple CAN monitor, without having to make write access to the bus (such as a scan of the network
by reading out parameter 0x1000).

Finally, the boot-up message communicates the end of the initialisation phase; the bus coupler signals that it
can now be configured or started.

Note



Up to firmware status BA the emergency identifier was used for the boot up message.