61

Identifier Allocation

Default identifier

CANopen provides default identifiers for the most important communication objects, and these are derived from
the 7-bit node address (the node ID) and a 4-bit function code in accordance with the following scheme:

For broadcast objects the node ID is set to ”0”. This gives rise to the following default identifiers:

Broadcast objects

Object Function

Function
Code

Resuting COB ID hex /
dez

Object for Comm. Parameter /
mapping

NMT

Boot-Up

0

0x00 / 0

- / -

SYNC Synchronisation 1

0x80 / 128

0x1005 + 0x1006 / -

Peer-to-Peer-Objects

Object

Function

Function
Code

Resulting COB ID hex /
dez

Objekt für Comm. Parameter /
Mapping

Emergency Status / Error

1

0x81 - 0xFF/ 129 - 255

- / -

PDO1 (tx)

dig. inputs

11

0x181 - 0x1FF / 385 - 511 0x1800 / 0x1A00

PDO1 (rx)

digital outputs

100

0x201 - 0x27F/ 513-639

0x1400 / 0x1600

PDO2 (tx)

analog inputs

101

0x281 - 0x2FF/ 641-767

0x1801 / 0x1A01

PDO2 (rx)

analog outputs

110

0x301 - 0x37F/ 769-895

0x1401 / 0x1601

PDO3 (tx)

analog inputs*

111

0x381 - 0x3FF / 897 -
1023

0x1802 / 0x1A02

PDO3 (rx)

analog outputs*

1000

0x401 - 0x47F/ 1025 -
1151

0x1402 / 0x1602

PDO4 (tx)

analog inputs*

1001

0x481 - 0x4FF/ 1153 -
1279

0x1803 / 0x1A03

PDO4 (rx)

analog outputs*

1010

0x501 - 0x57F/ 1281 -
1407

0x1403 / 0x1603

SDO (tx)

Parameters

1011

0x581 - 0x5FF/ 1409-1535 - / -

SDO (rx)

Parameters

1100

0x601 - 0x67F/ 1537-1663 - / -

Guarding Life-/Node-

guarding,
Heartbeat,
Boot-Up mes-
sage

1110

0x701 - 0x77F/ 1793-1919 (0x100C, 0x100D, 0x100E,

0x1016, 0x1017)

* For historical reasons, the Beckhoff default mapping applies to PDOs 3 and 4 in Beckhoff I/O devices. In most
configurations, PDOs 3 and 4 contain data related to analog inputs and outputs, but there can also be "excess"
data from digital I/Os, or data from special terminals. Details may be found in the Bus Coupler documentation.

Up until version 3 of the CANopen specification, default identifiers were assigned to 2 PDOs at a time. The
Beckhoff Bus Couplers correspond to this issue of the specification. After version 4, default identifiers are pro-
vided for up to 4 PDOs.