Format of the Boot-up message

11 bit identifier

1 byte of user data

0x700(=1792)+

node

ID

0x00

Node Monitoring

Heartbeat and guarding mechanisms are available to monitor failures in the CANopen network. These are of
particular importance for CANopen, since modules do not regularly speak in the event-driven mode of opera-
tion. In the case of "guarding", the devices are cyclically interrogated about their status by means of a data re-
quest telegram (remote frame), whereas with "heartbeat" the nodes transmit their status on their own initiative.

Guarding: Node Guarding and Life Guarding

Node Guarding is used to monitor the non-central peripheral modules, while they themselves can use Life
Guarding to detect the failure of the guarding master. Guarding involves the master sending remote frames
(remote transmit requests) to the guarding identifier of the slaves that are to be monitored. These reply with the
guarding message. This contains the slave’s status code and a toggle bit that has to change after every mes-
sage. If either the status or the toggle bit do not agree with that expected by the NMT master, or if there is no
answer at all, the master assumes that there is a slave fault.

Guarding procedure:

Protocol

The toggle bit (t) transmitted in the first guarding telegram has the value 0. After this, the bit must change (tog-
gle) in every guarding telegram so that the loss of a telegram can be detected. The node uses the remaining
seven bits to transmit its network status (s):

s

Status

4 = 0x04

Stopped (formerly: prepared)

5 = 0x05

Operational

127 = 0x7F

Pre-Operational

Example

The guarding message for node 27 (0x1B) must be requested by a remote frame having identifier 0x71B
(1819

dec

). If the node is Operational, the first data byte of the answer message alternates between 0x05 and

0x85, whereas in the Pre-Operational state it alternates between 0x7F and 0xFF.