3 handwheel operation feature, Figure 2.1 – electrical operation – Flowserve MX Electronic Actuator User Manual

Page 12

Advertising
background image

Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

12

Figure 2.1 – Electrical operation

NO ” operates

close direction

YES” operates

open direction

Enter “

SETUP ” mode

OPEN VALVE

RETURN TO STOP

OPEN VALVE

OK ?

SAVE OPEN

LIMIT OK?

SETUP?

CLOSE VALVE

RETURN TO STOP

SAVE CLOSE

LIMIT OK?

CLOSE VALVE

OK ?

CLOSE VALVE

OK ?

EXIT

SETUP?

100% OPEN

STATUS OK?

SET CLOSE

POSITION LIMIT?

YES

YES

YES

2

YES

YES

YES

YES

YES

2

NO

NO

NO

NO

NO

YES

1

NO

NO

NO

NO

STOP

STOP

STOP

LOCAL

Switch to

LOCAL

Switch to

OPEN VALVE

OK ?

SET OPEN

POSITION LIMIT?

YES

NO

NO

SET POSITION

PRECISION?

POSITION

XXX% OPEN?

YES

NO

NO

POSITION

XXX.X% OPEN?

NO

IDENTICAL LIMITS

KEEP OPEN LIMIT?

YES

NO

IDENTICAL LIMITS

KEEP CLOSE LIMIT?

YES

NO

YES

YES

YES

1

NOTE 1: If open and close limits

are not identical

NOTE 2: If open and close limits

are identical

2.1.3 Handwheel Operation Feature

To set the position limits manually, enter the “CHANGE SETTINGS” mode via the “SETUP” mode.

1. Enter the “SETUP” mode as detailed in Section 2.1.1, Entering the Setup Mode.

2. When LCD reads “CHANGE SETTINGS?”, select “YES.”

3. The LCD will display the “CHANGE SETTINGS” mode menu items. Select “NO” until screen displays “CHANGE

POSITION SETUP?”

4. Select “YES.” See Figure 2.2. Manually set position limits:

a. Close position limit

1. “SET CLOSE POSITION LIMIT?” is displayed.

2. Select “YES.” “CLOSE VALVE - OK?” is displayed.

3. Depress the declutch lever, and at the same time slowly rotate the handwheel until the clutch is fully

engaged. Release the lever; the clutch will be retained in the handwheel mode by spring-loaded latches.

4. Ensure the valve is fully closed, then move the valve in the open direction for one handwheel turn to allow

for coasting of the motor.

5. When the valve is in the desired position, select “YES” again. The LCD will read “SAVE CLOSE LIMIT OK?”

6. Select “YES” if the valve’s close limit position is correct. The close position limit is set.

b. Open position limit

1. “SET OPEN POSITION LIMIT?” is displayed.

2. Select “YES.” “OPEN VALVE - OK?” is displayed.