4.5 Torque Switch Timer

Torque switch timer permits a user to select a time for the torque switch to time out once the actuator determines that it
has reached its torque seat. The torque switch timer can be adjusted from one (1) second to a maximum of fifteen (15)
seconds. The default is five (5) seconds.

NOTE: It should be noted that the purpose of this feature is to ensure that the torque sensing has shut off the motor
after a brief period of time. It is an additional safety feature to prevent the actuator from reaching a stall torque.

If operating in torque seating for either open or close torque seating, a backup timer can be used to halt the actuator to
protect the valve in case the actuator does not torque out after it has passed the expected limit.

1. From “VALVE SETUP?” select “NO” to enter “CHANGE TORQUE TIMER” routine. This option will only appear if

either the open or close valve setting is set to torque seating.

2. Select “YES” to change setting. If “NO” is selected, the “POSITION SETUP?” routine will be entered.

4.5.1 Status

Default = ON

1. Select “NO” to change torque timer status to “OFF”. If “OFF” is selected you will not advance to timer selection for

that direction.

4.5.2 Torque Timer

The timer value is how long in seconds that the unit will run once it has passed the expected position limit.

Default = 5 seconds

1. Select “NO” to increase the timer value. The timer is configurable from 1-15 seconds. The counter will wrap around

to 1 second when you attempt to increase after 15 seconds.

NOTE: If the unit is only setup for open torque seating, then only the open torque timer will be available to change. This
is the same with close torque seating and the close torque timer. If both open and close torque seating are selected then
you will be prompted to change close torque timer first, followed by open torque timer.

Figure 4.6 – Torque Switch Timer

YES

1

YES

5

YES

2

YES

4

YES

YES

8

CHANGE

TORQUE SETUP?

CHANGE

TORQUE TIMERS?

CLOSE TORQUE

TIMER ON/OFF OK?

CLOSE TORQUE

TIMER #SEC OK?

OPEN TORQUE

TIMER ON/OFF OK?

NO

9

NO

YES

3

NO

10

YES

CHANGE

VALVE SETUP?

OPEN TORQUE

TIMER #SEC OK?

1 - 15 SEC

DEFAULT 5 SEC

1 - 15 SEC

DEFAULT 5 SEC

DEFAULT ON

DEFAULT ON

YES

YES

7

Note 1: YES & CLOSE Torque Seated

Note 2: YES & OPEN Torque Seated CLOSE Position Seated

Note 3: YES & TIMER OFF

Note 4: YES & TIMER ON

Note 5: YES & TIMER OFF & OPEN Torque Seated

Note 6: YES & OPEN Torque Seated

Note 7: YES & TIMER OFF

Note 8: YES & TIMER ON

Note 9: NO & Open or Close Torque Seated

Note 10: NO & OPEN/CLOSE Position Seated