Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

flowserve.com

“---% OPEN, FF NOT PRESENT” – FF board expected but not found

“---% OPEN, PBDP NOT PRESENT” – Profibus DP board expected but not found

“---% OPEN, PBPA NOT PRESENT” – Profibus PA board expected but not found

“---% OPEN, DN NOT PRESENT” – Device Net board expected but not found

“---% OPEN, ANG1 NOT PRESENT” – Analog 1 board expected but not found

“---% OPEN, ANG2 NOT PRESENT” – Analog 2 board expected but not found

“---% OPEN, CONTACTOR” – Contactor failure

“---% OPEN, ENCODER” – Encoder failure

“---% OPEN, R1R4RM RLY FAILED” – R1-R4 board relay check failed

“---% OPEN, R5R8 RLY FAILED” – R5-R8 board relay check failed

“---% OPEN, DDC FAILED” – Communication with the main board failed, or hardware fault

“---% OPEN, FF FAILED” – Communication with the main board failed, or hardware fault

“---% OPEN, PBDP FAILED” – Communication with the main board failed, or hardware fault

“---% OPEN, PBPA FAILED” – Communication with the main board failed, or hardware fault

“---% OPEN, DN FAILED” – Communication with the main board failed, or hardware fault

“---% OPEN, R1R4RM NOT AVAIL” – R1-R4 board expected but not found

“---% OPEN, R5R8 NOT PRESENT” – R5-R8 board expected but not found

“---% OPEN, ENCODER WARNING” – The encoder has not yet failed, but there was a momentary glitch detected.
If the glitch persists, encoder failure will be reported.

“---% OPEN, FF COM Lost” – FF enabled, signal absent

“---% OPEN, PB COM Lost” – PB enabled, signal absent

“---% OPEN, DN COM Lost” – DN enabled, signal absent

---%OPEN, ESD XX ACTIVE – Input # set for ESD, is asserted, and has highest priority

---%OPEN, ESD = XXX.X % = ESD ACTIVE and its action is “move to” ---.-% position

---%OPEN, ESD XX INHIBITED – Active ESD XX has been inhibited by an ESD override

---%OPEN, ESD XX CONFLICT – ESD XX is set for ESD, asserted, and is in conflict with the active ESD

---%OPEN, ESD OPEN – active ESD action is OPEN

---%OPEN, ESD CLOSED – active ESD action is CLOSED

---%OPEN, ESD STOP – active ESD action is STOP

---%OPEN, ESD IGNORE – active ESD action is IGNORE

--%OPEN, INHIBIT ACTIVE – INHIBIT signal is asserted

---%OPEN, INHIBIT CONFLICT – Conflict with multiple INHIBITs

---% OPEN, IDENTICAL LIMITS – Position limits identical preventing operation