4.12.6 Proportional Band

Proportional band is the range of errors between position and demand signal that will produce reduced speed (pulsing).

Default = 15%

To change from the default, select “NO” until the required value is displayed. The value is adjustable between 1% and
100%, in 1% increments.

4.12.7 Deadband

Default = 2%

The deadband should be wide enough to prevent “hunting” of the actuator but as low as possible to give adequate
response to changes in the error signal.

To Change from the Default Range:
Select “NO” to adjust the value between 1% and 50%, in 1% increments to suit the application.

Figure 4.17 – DN option

DNET ADDRESS

NET CTRL-OK?

ANALOG SCALE

(0-100)-OK

* If POSITION is chosen, as action,

this menu will appear.

YES

NO

(ON)

YES

NO

(CLOSE)

(OPEN)

(STOP)

(POSITION)

YES

NO

ESD ACTION

(IGNORE)-OK?

(CLOSE)

(OPEN)

(STOP)

(POSITION)

YES

NO

COMM LOSS ACTION

(NONE)-OK?

(0-4095)

YES

NO

(ASCII)

YES

NO

(0-100%)

*

*

YES

NO

MOVE TO

XXX% OPEN

(0-100%)

YES

NO

MOVE TO

XXX% OPEN

(2400-115.2K)

YES

NO

(1-250)

YES

NO

YES

NO

CHANGE PROP

DEAD BAND?

(1-100%)

YES

NO

PROP BAND

(8%)-OK?

(1-?%)

YES

NO

DEADBAND

(2%)

CHANGE

DEVICENET?

STATUS

(OFF)-OK?

BAUD RATE

AUTO-OK?

COMM LOSS DELAY

(60 SEC)-OK?

4.12.8 Comm Loss Delay

Default = 60 sec.

The User may select the amount of time delay before communication loss is flagged to the network. This selection is
configurable from 120 seconds.

4.12.9 Comm Loss Action

Default = None

The User may select what action the actuator should take when network communication is interrupted. This action is