4.18.7 Overtorque*

Default = OVERTORQUE>ESD

To Customize the Settings:
Select “NO” to choose:

• “ESD>OVERTORQUE” – ESD overrides overtorque situation
• “OVERTORQUE>ESD” – Overtorque situation overrides ESD
* See CAUTION on Figure 4.24.

4.18.8 Motor Thermostat

Default = THERMOSTAT>ESD

To Customize the Settings:
Select “NO” to choose:

• “ESD>THERMOSTAT” – ESD overrides Motor Thermostat tripped
• “THERMOSTAT>ESD” – Motor Thermostat tripped overrides ESD
NOTE: Disabling the motor thermostat voids all third party certifications including Factory Mutual, CSA, ANZex, IECEx
and ATEX. Disabling the motor thermostat removes protection from overheating the motor and may cause unsafe
conditions.

4.18.9 Oil Over Temperature

Default = OIL OVERTEMP>ESD

To Customize the Settings:
Select “NO” to choose:

• “ESD>OIL OVERTEMP”– ESD overrides high oil temperature
• “OIL OVERTEMP>ESD” – High oil temperature overrides ESD

4.18.10 Two-speed Timer

Default = 2SPD > ESD

To Customize the Settings:
Select “NO” to choose:

• “ESD > 2SPD” - ESD overrides 2 speed timer
• “2SPD > ESD” - 2 speed timer overrides ESD

4.18.11 Network ESD

Default = LOCAL ESD > NW ESD

To Customize the Settings:
Select “NO” to choose:

• “NW ESD > LOCAL ESD” - Network ESD overrides Local ESD
• “LOCAL ESD > NW ESD” - Local ESD overrides Network ESD