Flowserve MX Electronic Actuator User Manual

Page 79

Advertising
background image

79

Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

flowserve.com

Input 3 (normal default - stop) terminal 26:
• Set as enabled, ESD release function, signal absent = active

Input 4 (normal default - open) terminal 25:
• Set as enabled, ESD Release function, signal present = active

Input 5 (normal default - close) terminal 27:
• Set as enabled, momentary ESD/PSESD function, signal present> 800 ms = active, ESD action =

Close, partial stroke target position = 0% open The ESD release signals are setup as redundant signals for safety. There
are two signal inputs, and BOTH must be in the active state. If there is an active ESD and both ESD release inputs are in
the active state, the ESD will be unlatched and the unit will return to normal operation. If the ESD release inputs are in
a fault state, an active ESD will NOT be released. The ESD release inputs will have no effect on a partial stroke ESD test.
The momentary ESD/PSESD input will be ignored if there is a signal present for less than 100 ms, and is guaranteed to
latch in the ESD/PSESD if the signal is present for greater than 800 ms. Once the ESD is latched in, the unit will perform
the ESD action. In this case the ESD will move the unit to the close limit and remain in ESD mode until the ESD release
indication is given using the ESD release inputs.

Figure 4.33 – SIL control (Enhanced)

SIL CONTROL

ENHANCED?

STATUS

(OFF)-OK?

STATUS

(OFF)-OK?

STATUS FUNC

USER INPUT-OK?

SIGNAL

PRESENT-OK?

CHANGE

OUTPUT 0?

CHANGE

INPUT-0?

VIEW

DIAGNOSTICS?

YES AND

2 WIRE

OPEN INHIBIT

CLOSE INHIBIT

BOTH INHIBIT

2-WIRE OPEN

2-WIRE CLOSE

NOTES:

NOTE 1: 2 Wire controls are not selectable is DDC, PBCP, PBPA,

Devicenet, FF, or Maclulating controls are enabled.

SEE NOTE 1

YES AND

NOT 2 WIRE

SEE NOTE 1

ABSENT

YES AND NOT POSITION

IGNORE

CLOSE

OPEN

STOP

YES

YES

YES

OFF

YES

YES

YES

YES

YES

YES

YES

ABSENT

NO

NO

NO

NO

STATUS FUNC USER

MO ESD/PSESO-OK?

NO

SIGNAL

PRESENT-OK?

NO

ESD ACTION

POSITION-OK?

NO

ESD MORE TO

XXX%-OK?

NO

PROP BAND

XXX%-OK?

NO

DEAD BAND

XXX%-OK?

NO

PS MOVE TO

XXX%-OK?

NO

YES

Advertising
This manual is related to the following products: