4 setting position limits – Flowserve MX Electronic Actuator User Manual

Page 34

Advertising
background image

Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

34

5. When configuration is complete, answer “YES” to “EXIT SETUP?” or move the red knob from “STOP” to “LOCAL”

or “REMOTE.”

After exiting the “SETUP” mode, all settings will automatically be saved to a non-volatile memory and retained, even
when power is removed from the actuator. However, if power is removed from the unit while the unit is in “SETUP”
mode, customization changes will be lost.

Figure 3.22 – View settings

VIEW

VALVE SETTINGS?

1

VIEW

SETTINGS?

YES

NO

NO

YES

YES

VIEW

FF?

NO

YES

NOTE 1: These optional displays

will not appear unless the

option has been purchased.

NOTE 2: If enabled.

NO

YES

NO

YES

NO

YES

NO

YES

VIEW

LOCAL CONTROL?

NO

YES

YES

YES

NO

VIEW

PB/DP?

VIEW 2-SPEED

TIMERS?

VIEW STATUS &

ALARM CONTACTS?

NO

YES

NO

YES

NO

YES

NO

See

NOTE 1

See

NOTE 1

See

NOTE 1

YES

NO

1

YES

YES

NO

NO

NO

YES

YES

NO

VIEW

ANALOG OUT?

VIEW

PB/PA?

VIEW

DEVICENET?

See

NOTE

1

See

NOTE

See

NOTE

1

1

See

NOTE

See

NOTE

VIEW

REMOTE MODE?

VIEW ESD

OVERRIDES?

VIEW

MONITOR RELAY?

VIEW

INPUTS?

VIEW

TORQUE BOOST?

VIEW

THERMOSTAT?

VIEW

VALVE DATA?

VIEW

PORTS?

YES

VIEW BACK-UP

POWER?

VIEW

UNIT DATA?

VIEW

MODUTRONIC?

VIEW TORQUE

SETTINGS?

See

NOTE 1

See

NOTE 2

YES

YES

NO

See

NOTE 1

YES

NO

NO

VIEW TORQUE

TIMER?

YES

NO

VIEW

DDC?

3.5.4 Setting Position Limits

This section will advise how to configure end-of-travel limits.

The actuator’s position limits may be set by manual operation or electrical operation.

c

WARNING: If the actuator will not move after setting the limits, the limits have been set incorrectly.

Set Close Position Limit (Handwheel Operation)
1. Enter the “SETUP” mode as detailed in Section 2.1.1, Entering the Setup Mode.

2. Enter “POSITION SETUP?” routine.

3. From the “SET CLOSE POSITION LIMIT?” display, select “YES.” “CLOSE VALVE OK?” will be displayed on the LCD.

4. Engage manual override as detailed in Section 3.6.1, Manual Operation.

5. Ensure that the valve is fully closed.

6. Move the valve in the open direction for one handwheel turn to allow for coasting of the motor.

7. When the valve is positioned correctly, select “YES” again. The LCD will display “SAVE CLOSE LIMIT OK?”

8. Select “YES.”

The close position limit is now calibrated. Check the position limit setting as follows:

1. Move the valve in the open direction. The close lamp should extinguish with approximately one turn of the

handwheel.

Advertising
This manual is related to the following products: