Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

flowserve.com

4.9.2 Network Address

Default = 1

Network address allows user to assign a unique network address to an actuator.

1. The network address must be entered in accordance with the Instrument Data Sheet, and care must be taken to

ensure that the same address is not used anywhere else in the same network.

2. Select “NO” for small incremental changes or hold it continuously in that position for larger changes until the

required value is displayed. The address may be set at any value between 001 and 250.

4.9.3 Protocol

Default = Modbus RTU 9600 Baud

Protocol changes the communication language/speed from the default to match the application.

To Change from the Default Language:
Select “NO” to choose between MODBUS, ASCII, or RTU, and the baud rate depending on the design of the DDC
system. Refer to the contract documentation.

4.9.4 Analog Scale

Default = 0-100

Analog scale allows the user to change the scaling of the analog input from the default.

To Change from the Default Range:
Select “NO” until the required scale is displayed. 0-255 and 0-4095 counts are available.

4.9.5 ESD Action

A network ESD function can be enabled after the ESD configuration has been established for the unit. This network ESD
can be selected to either ignore the command; Close, Open, Stop, or Position the actuator.

Figure 4.13 – DDC

YES

NO

CHANGE

DDC?

(ON)

YES

NO

STATUS

(OFF)-OK?

(CLOSE)

(OPEN)

(STOP)

(POSITION)

YES

NO

ESD ACTION

(IGNORE)-OK?

(CLOSE)

(OPEN)

(STOP)

(POSITION)

YES

NO

COMM LOSS ACTION

(NONE)-OK?

(0-4095)

YES

NO

COMM LOSS DELAY

(60 SEC)-OK?

(ASCII)

YES

NO

MODBUS

RTU-OK?

(0-100%)

*

*

YES

NO

MOVE TO

XXX% OPEN

(0-100%)

YES

NO

MOVE TO

XXX% OPEN

(2400-19.2K)

YES

NO

BAUD RATE

9600-OK?

(1-250)

YES

NO

DDC ADDRESS

1-OK?

(0-255)

(0-4095)

YES

NO

ANALOG SCALE

(0-100)-OK

YES

NO

CHANGE PROP

DEAD BAND?

(1-100%)

YES

NO

PROP BAND

(8%)-OK?

(1-?%)

YES

NO

DEADBAND

(2%)

* If POSITION is chosen, as action, this

menu will appear.

NOTE: These settings are the same for

multi-drop standard DDC on main board

and DDC network board. If customer has

both, then they will have the same

settings.