17 remote mode, 1 local control – Flowserve MX Electronic Actuator User Manual

Page 68

Advertising
background image

Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

68

4.17 Remote Mode

Remote mode permits a User to select from multiple remote control permissions, or isolate remote control to a single
control selection:

• Multi Control mode (default): There are three modes of remote control for the MX actuator allowed when the remote

mode is configured for multi-control: digital control, analog control, and network control. Digital and network control
operation is based on the last command received. Analog control operation in initiated by either toggling user input 2
(configured for CSE input) or breaking and reapplying the analog signal.

• Digital Control Only: the unit will operate only upon the last digital input command received.
• Network Control Only: the unit will operate only upon the last network command received.
• Analog Control only: the unit will operate only upon the last analog input command received.

Figure 4.26 – Remote mode

NO

YES

YES

NO

CHANGE

REMOTE MODE

MULTI-CONTROL

MODE - OK?

NO

YES

YES

NO

DIGITAL

CONTROL ONLY?

NETWORK

CONTROL ONLY?

YES

NO

ANALOG

CONTROL ONLY?

4.17.1 Local Control

“LOCAL CONTROL” mode changes how the local control switches and display are used from the default settings.

Default = On & Maintain Mode

NOTE: User may select to disable the LOCAL CONTROL, which prohibits the cycling of the MX from OPEN to
CLOSE or REVERSE. The LOCAL-STOP-REMOTE knob still functions, which permits the user to re-enter set-up and
turn the LOCAL CONTROL back to “ON.”

Figure 4.27 – Local control

NO

YES

YES

NO

YES

YES

NO

RED/GREEN LED

NORMAL-OK?

CHANGE

LOCAL CONTROL?

RED/GREEN LED

REVERSED-OK?

MODE

(MAINTAIN)-OK?

YES

NO

(Inching)

STATUS

ON-OK?

Advertising