Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

26

Particular care should be taken when terminating twisted-pair shielded cables in a control network. Avoid nicks, cuts, or
abrasions in the insulation of data communication cables, since this may result in inadvertent ground connection. Also,
excess cable should be cut, not coiled or looped, to prevent noise induction into the network.

Limitorque strongly recommends remote communication wiring be routed separately from mains line power wiring.
Specifically, instrumentation wiring, including communication, analog and discrete signal wiring, should be routed
in conduit that is separated from power lines. If the recommendation is not followed, the intergrity of instrumenta-
tion signals may be comprimised. If the signal is comprimised, the MX will enter a“safe-state” whereby all motion is
prohibited until communication is sucessfully re-established.

Figure 3.13 – View of terminal block

Figure 3.14 – Standard wiring diagram
NOTE: Most current wiring diagram is shipped within the terminal compartment of the MX.

Cable Preparation
Prepare the network cable for connection to the MX actuator terminal block as illustrated in Figures 3.15 through 3.18.

a

CAUTION: Strip stranded conductors carefully; do not damage the strands. This will weaken the conductor.
Do not nick conductors when stripping away the insulation. Nicking stresses the conductor and can cause the
conductor to break. This type of damage may not be apparent and failure can occur later without warning.

Configurable SET-UP to give;
Either
-Contact closed-Valve OPEN S
-Contact opened-Valve CLOSE
OR :
-Contact closed-Valve CLOSES
-Contact opened-Valve OPEN S

3-WIRE

4-WIRE

INHIBIT

ESD

5

7

5

6

7

9

10

21

INTERNAL

SUPPLY

110V AC

8

5

7

12

8

11

5

6

7

8

12

8

11

5

7

13

8

14

5

6

7

13

8

14

8

8

9

10

21

12

12

9

10

21

13

13

8

14

8

14

5

CLOSE

STO P

6

OPEN

7

CONTROL COMMON

8

11

0V AC

110V AC

12

+24V DC

13

0V DC

14

10

OPEN INHIBIT

CLOSE INHIBIT

9

ESD

21

FUNCTIO N

POIN T

TERMINAL

EXTERNAL

SUPPLY

24 TO 110

VOLT

AC/D C

8

11

8

11

AC/DC

0V

AC/D C

24-110V

AC/D C

0V

AC/DC

24-110V

AC/D C

0V

AC/D C

24-110V

AC/D C

0V

AC/DC

24-110V

EXTERNAL SUPPLY

Configurable SET-UP to give;
Either
-OPEN/CLOSE push-to-run
(inching) mode OR
-OPEN/CLOSE push and release
(maintained) mode with mid-
travel reversal
(Stop before reverse)

mid-travel stop

reversal and

with mid-travel

(maintained) MODE

Push-and-release

OPEN/STOP/CLOSE

close contacts

maintained open or

interlock/inhibit on

SET-UP to give;

Configurable during

CLOSED/OPEN/STOP/IGNORED

maintained ESD signal:

ACTIONS on receipt of a

to give following modes of

Configurable during SET-U P

REMOTE WIRING CONNECTIONS

7

8

2-WIRE

7

12

8

11

7

13

8

14

AC/D C

0V

AC/D C

24-110V

OUTPUT SWITCH CONTACT DEVELOPMENT

VALVE POSITIO N

FULL
CLOSE

FULL
OPEN

FUNCTIO N

CLOSE LIMIT

AS4

OPEN LIMIT

AS 3

CLOSE LIMIT

OPEN LIMIT

AS1
AS2

SWITCH

OUTPU T

INTERNAL

SUPPLY
24V DC

Grounding lug

View of terminal block

Reversing

contactor

Close

Stop

Open

Dig Com #1-Ve

Close inhibit/

interlock Input 1
interlock Input 2

Open inhibit/

Dig Com #2-Ve

0 VAC

110 VAC

24 VDC +Ve

0 VDC

24 VDC +Ve

0 VDC

27
26
25

35

28

29

34

24

23

21

22

7

6

L1

L2

L3

FS1 FS2

FS3

LimiGard

Motor

board

Power

PE

Three-phase supply

Control

supply

Aux.

input

(Optional)

*

E.S.D. Input 0

Dig Com #3-Ve

32

30

Position

sensor

44

45

48

49

46

47

50

51

S1a

S1b

S2a

S2b

CLOSE

position

OPEN

position

54

53

52

Show n

with

power

supply off

Control panel

Torque

sensor

Monitor relay

Circuit shown with valve in fully

closed position and with power off.

Main processor board

Status feedback

output switches

Default setting

CLOSE

position

OPEN

position

CLO

SE

STOP

OPEN

(YES

)

REMO

TE

LOCAL

(NO

)

Limitorque

*

Jumpers may be added to connect digital commons - pt. 28 & 29, 31& 32

Note: 110 VAC control supply from actuator is optional.