9 sil mode – enhanced sil (optional), Figure 4.32 – sil control (standard) – Flowserve MX Electronic Actuator User Manual

Page 78

Advertising
background image

Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

78

Figure 4.32 – SIL control (standard)

4.19.9 SIL Mode – Enhanced SIL (Optional)

Custom software is available for the MX that permits the User to establish certain performance characteristics for partial
stroke (PS) testing and momentary contact closure ESD.

NOTE: These three inputs are normally configurable. When this SIL mode is enabled, input 0 is configurable to 2 wire
control, user defined or inhibit. Inputs 1 and 2 are pre-configured for partial stroke enable and cannot be changed by
the customer.

Input 0 (normal default - ESD) terminal 30:
• Set as disabled, user input function, signal present

Input 1 (normal default - Open Inhibit) terminal 34:
• Set as enabled, partial stroke enable function, signal present = active

Input 2 (normal default - Close Inhibit) terminal 35:
• Set as enabled, partial stroke enable function, signal absent = active

The partial stroke enable signals are setup as redundant signals for safety. There are two signal inputs, and BOTH must
be in the active state. If the partial stroke enable inputs are in the active state, and an input is detected (>800 ms) on the
momentary ESD/PSESD input, then a partial stroke ESD test will be run. If the partial stroke enable inputs are not active
or in a fault state, and an input is detected on the momentary ESD/PSESD input, then the ESD will be latched in and the
actuator will perform ESD until the ESD Release is given.

NOTE: These three inputs are the normal open-close-stop inputs. When this custom mode is enabled, they are set to
the predefined configuration and cannot be changed by the customer. The only change the customer can make is to
set the momentary ESD action (if action is position - then also the target value for the ESD) and the partial stroke target
value.

SIL CONTROL

STANDARD?

STATUS

(ON)-OK?

STATUS FUNC

ESD-OK?

MODE

USER INPUT?

CHANGE

INPUT-0?

CHANGE

INPUT 1?

NOTE 1: Input 2 can be configured like any standard input, i.e. inhibits. ESO, user input

NOTE 2: The ESO MOVE TO menu only appears of position is chosen an action.

SEE NOTE 2

SEE NOTE 1

ABSENT

STOP

OPEN

CLOSE

IGNORE

4-Wire

3-Wire Main

3-Wire Inch

2-Wire

User Input

YES

NO

YES

OFF

YES

YES

YES

YES

YES

YES

YES

CHANGE

INPUT-2?

SAVE

SETTINGS?

NO

SIGNAL

PRESENT-OK?

NO

ESD ACTION

POSITION-OK?

NO

MOVE TO

XXX%-OK?

NO

PROP BAND

XXX%-OK?

DEAD BAND

XXX%-OK?

NO

NO

STATUS

(ON)-OK?

ABSENT

YES

YES

OFF

YES

YES

YES

YES

YES

STATUS FUNC

PARTIAL STROKE

NO

SIGNAL

PRESENT-OK?

NO

PS MOVE TO

XXX%-OK?

NO

PROP BAND

XXX%-OK?

NO

DEAD BAND

XXX%-OK?

NO

Advertising