SMTS Technical Guide

VCM & VCM-X Controllers

27

VCM & VCM-X Confi guration

Emergency Shutdown Enabled

Select this item if an emergency shutdown device is connected to the
binary input. If the shutdown is active, the Supply Fan, Heating, and
Cooling Relay outputs will be disabled.

Has Building Pressure Mod Control

Select this item if your system needs Modulating Building Pressure Con-
trol. Modulating building pressure control is used for a VFD exhaust fan
or a modulating exhaust fan damper actuator for direct acting building
pressure control. Modulating building pressure control is also used for a
modulating outdoor air damper actuator or a supply fan VFD for reverse
acting building pressure control.

Building Pressure Reverse Acting

Select this item if your system needs Reverse Acting Building Pressure
control. On a drop in Building Pressure below the Building Static Pres-
sure Setpoint the Outdoor Air Damper will modulate open to increase
pressure or the supply Fan VFD will ramp-up.

Building Pr. Output is 2-10 VDC

Select this item if your application needs a 2-10 VDC Building Pressure
Output Signal as required by the device you are using to control the pres-
sure. Do not select this item if your application needs a 0-10 VDC signal.

Use Heat During Re-Heat

Select this item if your application needs to use unit heat during Dehumidi-
fi cation to supplement Reheat. If Reheat is not available, this selection
will allow the unit heat to operate in place of Reheat.

Outdoor Air Damper Control Based on Airfl ow CFM

Select this item to modulate the outdoor damper based on airfl ow setpoint.

Head Pressure Module Installed ( VCM-X Modular, VCM-X

WSHP)

Select this item if you have a Head Pressure Module installed on your
system.

Has Modulating Cooling

Select this item if the HVAC unit is controlling Modulating Cooling
through use of a modulating chilled water valve or a digital compressor.

Modulating Cooling is Reverse Acting

Select this item if Modulating Cooling requires 0 VDC to open and 10
VDC to close. You cannot use a reverse acting signal your application is
using a digital compressor.

Has Modulating Heating

Select this item if the HVAC unit is controlling Modulating Heating
through use of a modulating hot water valve, modulating steam valve,
or a SCR controlled electric heater.

Modulating Heating is Reverse Acting

Select this item if Modulating Heating requires 0 VDC to open and 10
VDC to close.

Has Return Bypass Control

Select this item if your HVAC unit requires Return Air Bypass Control.

Full Digital Module Installed, Dual Digital Module Installed,

or using VCM-X WSHP Controller (VCM-X Modular or VCM-X

WSHP)

Select this item if you have multiple Digital Scroll Compressors installed
on your system.

Has Demand Ventilation Control

Select this item if the HVAC unit has demand ventilation control.

Has Split Condensers

Select this item if the HVAC unit has split condensers.

Broadcast Real Time Clock to VAV Boxes

Select this item to have the HVAC unit broadcast the real time clock to
all controllers on its local loop. This broadcast sends the time from the
VCM-X’s Internal Time Clock to all controllers on its local loop. This
broadcast needs to be confi gured on a VAV or Zoning System using the
VCM-X with Orion VAV/Zone controllers. A network communications
device is required in order for this feature to operate, but can also be used
to synchronize all controllers on the local loop

Broadcast Supply Air to VAV Boxes

Select this item to broadcast the VCM-X’s Supply Air Temperature to
all controllers on its local loop. This broadcast needs to be confi gured
on a VAV or Zoning System using the VCM-X with Orion VAV/Zone
Controllers. A network communications device is required in order for
this feature to operate.

Broadcast AHU Schedule to VAV Boxes

You must select this item if you have VAV/Zone controllers connected
to the VCM-X controller. This will broadcast the Occupied and Unoc-
cupied Schedule of the VCM-X controller to all VAV/Zone controllers
on the local loop.

Broadcast Main Fan and Heat Status to VAV Boxes

Select this item to broadcast the VCM-X’s Supply Fan and Heating Status
to all controllers on its local loop. This broadcast needs to be confi gured
on a VAV or Zoning System using the VCM-X with Orion VAV/Zone
Controllers. A network communications device is required in order for