SMTS Technical Guide

VCM, VCM-X & VCB-X Controllers

39

VCB-X Controllers

Building Pressure Control

This confi guration option is available if the EM1 Module has been
installed and confi gured. Touch the radio button to select type of Building
Pressure Control. Default is None.



None—

No Building Pressure Control by this controller.

 

On/Off Control—

If the building pressure rises above

setpoint, a relay confi gured as Exhaust Fan will energize in

order to turn on an On/Off exhaust fan. You must confi gure

one of the output relays as Exhaust Fan.

 

Modulating Control—

If the building pressure rises above

setpoint, a modulating signal will be used to control an

exhaust fan VFD or a modulating damper. A relay

confi gured as Exhaust Fan can be used to enable this device

so that the modulating signal can control it.

 

Reverse Acting OA Damper Control

—Select if reverse

acting Building Pressure Control using the Outdoor Air

Damper is required. If the building pressure falls below

setpoint, the OA Damper (Economizer) signal will be used

to modulate the OA Damper to maintain setpoint.

 

Reverse Acting Supply Fan VFD Control

—Contact

WattMaster Factory regarding this reverse acting Building

Control option. This should not be used in most

applications.

Morning Warm-Up

Touch the radio button to select type of Morning Warm-Up control.
Default is None.



None

— There is no Morning Warm Up required.

 

Stand Alone Warm-up Control

The VCB-X Controller

is not communicating to Orion VAV Box controls, but a

Morning Warm Up Relay can be confi gured to signal boxes

by other to open.

 

Warm-up w/Broadcast to Fixed Airfl ow—

The VCB-X

Controller is communicating to Orion VAV Boxes and will

broadcast a command to the boxes to go to a Fixed

Percentage Position or Airfl ow while in Morning Warm Up.

This

fi xed position is confi gured in the VAV box controller.

 

Warm-up w/Broadcast to Maximum Airfl ow—

The

VCB-X Controller is communicating to Orion VAV Boxes

and will broadcast a command to the boxes to go to a

Maximum Percentage Position or Airfl ow while in Morning

Warm Up. This maximum position is confi gured in the VAV

box

controller.

Binary Input Confi guration

Touch the square button to select the binary inputs on the VCB-X
Controller.

Emergency Shutdown Input is Required

Select this item for YES if a Smoke Detector/Firestat
or other Emergency Shutdown input is connected to the
Emergency Shutdown binary input. If a Shutdown condition
occurs and the 24V signal is removed from this input, the
Supply Fan and Heating and Cooling Relay Outputs will be
de-energized and an alarm will be generated. Default is NO.

VCB-X Confi guration

Proof of Flow Input is Required

Select this item if the unit is equipped with a Proof of Flow
Switch and it is connected to the VCB-X. If selected as
YES and the Proof of Flow Switch is open, only the Supply
Fan Relay will be active. If any other relays such as Heating
Stages or Cooling Stages are active, they will be deactivated
when the Proof of Flow Switch input is lost. Default is NO.

Dirty Filter Input is Required

Select this item if a Dirty Filter switch is connected to the
Dirty Filter binary input. If the Dirty Filter input is active,
an alarm will be generated. Default is NO.

Defrost Coil Switch Installed

Select this item if a Defrost Coil Temperature Switch is
installed and is connected to the Defrost Coil Temperature
Switch binary input. If this switch closes, it will initiate a
Defrost Mode. Default is NO.

Installed Sensors

Touch the square button to select the desired airfl ow sensor monitoring:

Monitor Return Airfl ow Sensor—

Select

this item if

you have an Airfl ow Monitoring station

measuring the CFM

of the Return Air airfl ow stream of this unit

. Default is NO.

Monitor Supply Airfl ow Sensor—

Select

this item if

you have an Airfl ow Monitoring station

measuring the CFM

of the Supply Air airfl ow stream of this unit

. Default is NO.

Monitor Exhaust Airfl ow Sensor—

Select

this item if

you have an Airfl ow Monitoring station

measuring the CFM

of the Exhaust Air airfl ow stream of this unit

. Default is NO.

Monitor Outdoor Airfl ow Sensor—

Select

this item if

you have an Airfl ow Monitoring station

measuring the CFM

of the Outdoor Air airfl ow stream of this unit

. Default is NO.

Control Outdoor Airfl ow—

Select

this item if

you have an Airfl ow Monitoring station and are controlling the

OA Damper to an airfl ow (CFM) setpoint. Default is NO.

Has Outdoor Air Temperature Sensor—

Select

this

item if you have any type of Outdoor Air Temperature Sensor

installed.

Broadcast Outdoor Air Humidity—

The VCB-X will

broadcast its Outdoor Air Humidity Reading to other HVAC

units if they are not equipped with their own Outdoor Air RH

sensors. A network communications device (MiniLink PD or

CommLink) is needed in order for this feature to operate.

Broadcast Outdoor Air Temperature—

The VCB-X will

broadcast its Outdoor Air Temperature Reading to other HVAC

units if they are not equipped with their own Outdoor Air

Temperature sensors. A network communications device

(MiniLink PD or CommLink) is needed in order for this feature

to

operate.