Vcm, vcm-x & vcb-x controllers, Vcb-x controllers vcb-x confi guration, Smts technical guide 36 – Orion System OE392-10 System Manager TS User Manual

Page 36

Advertising
background image

Zone

Zone

VCM, VCM-X & VCB-X Controllers

SMTS Technical Guide

36

VCB-X Controllers

VCB-X Confi guration

VCB-X Confi guration

Touch the

< Confi guration>

button to access the Confi gu-

ration Setpoints Screens.

For screens that contain radio buttons, touch the radio
button next to your selection. For screens with square

buttons, touch one or more square buttons to make your confi guration
selections for the unit.

Check this Box for Celsius Temperature Scaling—

Touch

the square button to select Celsius Temperature Scaling. Default

is

Fahrenheit.

Installed Sensors

Touch the square button to select the sensors that are installed:

Carbon Dioxide Sensor Installed

Suction Pressure Sensor Installed

Communicating Indoor Sensor Installed

—This is the

E-BUS Digital Room Temperature Sensor or Digital

Temperature and Humidity Sensor.

Communicating Outdoor Sensor Installed

—This is

the E-BUS Outdoor Air Temperature and Humidity Sensor.

Installed Expansion Boards and Modules

Touch the square button to select the Expansion Board(s) and Modules
that are installed. The available selections are as follows:

Main Expansion Board Installed

—This is the

EM1 Module. The following IO is available on EM1:

 

VAV Capabilities

 

Water Temperature

 

Building Pressure

 

Hood On/Off

 

Head Pressure Control

 

Proof of Flow

 

Return Air Temperature

 

Condenser Control

 

Remote Forced Occupied

 

Water Source Heat Pump Monitoring

 

Modulating Chilled Water

ReHeat Expansion Board Installed

—This is the

MHGRV-X

Controller.

Mod Gas Expansion Board Installed

—This is the

MODGAS-X

Controller.

12 Relay Expansion Board Installed

—This is the

E-BUS 12 Relay Expansion Module.

Config

HVAC Mode Enable Source

Touch the radio button to select the Temperature Sensor/Application that
will determine the Heating, Cooling, or Vent Mode of operation. Default
is Single Zone VAV. The available selections are as follows:

Single Zone VAV

—Recirculating unit using the Space

Temperature Sensor to determine the mode of operation.

Heating and Cooling are controlled to a Leaving Air

Setpoint. Space Temperature resets the Supply Fan VFD

speed to maintain the Space Temperature. Modulating

Heating and Cooling must be used for VAV operation.

Can be confi gured for CAV Heating using staged Heat.

Space Temperature

—Typical recirculating unit using a

Space Temperature Sensor to determine the Heating,

Cooling, and Vent Modes of operation.

Outdoor Air Temperature

—This is for a 100% Outdoor

Air Unit (MUA) using the Outdoor Air Temperature Sensor

to determine the Heating, Cooling, and Vent Modes of

operation. Dehumidifi cation utilizes an Outdoor Air

Dewpoint

Setpoint

Supply Air Cooling Only

—This is for a standard Cooling

Only VAV unit with optional Morning Warm Up. In the

Occupied Mode, the unit will be in the Cooling Mode

controlling to the Cooling Supply Air Setpoint.

Return Air Temperature

—Optional recirculating unit

confi guration using the Return Temperature Sensor to

determine the Heating, Cooling, and Vent Modes of

operation.

Static Pressure Control

This confi guration option is available if expansion module EM1 is
installed and confi gured. Default is Fan VFD. The options are:

None

—This unit is not controlling Duct Static Pressure.

Fan VFD or Single Zone VAV

—This unit has a Supply

Fan VFD that modulates to control the Duct Static Pressure.

Bypass Damper

This unit uses a Bypass Damper to

control the Duct Static Pressure.