MGA 6010 Operations Manual

Super Systems Inc.

Page 41 of 54

12.

Wait for the “Current Value” displayed on the screen to get as close as possible to the voltage

being delivered by the millivolt sourcing device.

13.

Tap Calibrate. Tap “Yes” when asked if you want to proceed with the calibration. A progress

indicator will appear.

14.

When the process completes, Span calibration is finished.

To perform a temperature calibration (“Cold Junction Trim”):

Needed:

Thermocouple wire type “S” and/or “K”, temperature sourcing device

1.

Open the Analog Input Calibration page.

2.

Make sure that the selected input at the top of the screen is T/C K or T/C S, depending on which

thermocouple wire type you are using.