Temperature controller connection, Must – TE Technology TC-48-20 User Manual

Page 18

Advertising
background image

18

TE Technology’s standard thermoelectric cooling assemblies (TCA) usually have at least one fan on the heat 
sink. The standard configuration has the thermoelectric modules and fan(s) wired to a terminal block with 
jumpers  across  the  terminals  so  that  the  fans  and  TE  modules  are  connected  electrically  in  parallel. 
However, this configuration is applicable only when applying power directly from the power supply. When 
using the  TCA with  the  temperature controller,  two  jumpers

 MUST

 be  removed  so  that  the controller  is 

controlling power only to the thermoelectric modules. There must be no electrical connection between the 
fans and the TE modules; fans must be connected directly to the power supply, not to the controller. The 
controller  will  be  damaged  if  this  is  not  followed
.  See  the  TCA  manual  for  further  details,  but  the  picture 
below shows the basic setup.

  

 

 

 

 

 

Temperature Controller Connection

PROTECTION

DEVICES

DC POWER SUPPLY

THERMOELECTRIC

(PELTIER)

HOT-SIDE FAN

(ALL UNITS)

COLD-SIDE FAN

(AC-XXX UNITS ONLY)

TCA

TEMPERATURE

CONTROLLER

Terminal Block

Cover removed

for clarity. Re-

install before

operation.

Review electrical jumper connections. Remove electrical jumpers as required.