TE Technology TC-48-20 User Manual

Page 24

Advertising
background image

24

Description:  This  setting  determines  what action  will  be taken  when  there  is  an alarm  condition  on  the 
secondary sensor. When KEEP OUTPUT ON is selected, output power to the TE device stays on during the 
alarm  condition,  and  the  alarm  2  signal  on  JP5‐11  is  activated.  When  TURN  OFF  OUTPUT  is  selected, 
output power to the TE device is turned off, and the alarm 2 signal on JP5‐11 is activated. 
 

The ALARM 1 and ALARM 2 outputs on JP5‐10 AND JP5‐11 will momentarily pulse on and off 
several times in the first second after the controller is turned on.  This happens as the 
microprocessor in the controller configures itself, regardless of any alarm condition. 

 

2.3.13 ALARM LATCHES 

Values: NO LATCHES, ALARMS 1&2 LATCH, ALARM2 LATCH, ALARM1 LATCH 

 

Default value = NO LATCHES 
 
Descriptions: 
NO LATCHES: If an alarm condition occurs but then clears itself, the alarm signal will automatically turn off 
and power to the TE device will be restored (if ALARM 1 FUNCTION and ALARM 2 FUNCTION are set to 
TURN OUTPUT OFF).  

If the alarm condition is recurring and the ALARM 1 FUNCTION and/or ALARM 2 FUNCTION is set 
to  TURN  OUTPUT  OFF,  the  TE  device  can  be  damaged  by  thermal  fatigue  stress  imposed  by 
repeated long‐term power cycling. 

 
NOTE:  The  default  deadband  for  the  latch  reset  is  0  °C.  However,  the  deadband  can  be  reprogrammed 
using  the  RS232  interface  to  allow  for  the  latch  to  reset  at  a  specified  temperature  difference 
above/below the alarm set point. You can use the software provided with the controller or you can create 
your  own  software  and  use  the  controller  commands  as  described  in  “Serial  Communications”  in  the 
appendix. 
 
ALARMS 1&2 LATCH: if an alarm condition occurs from either the control or secondary sensor or both, the 
controller will continue to signal an alarm until reset, even if the alarm condition is cleared. Power to the 
controller must be turned off and then on again to turn off the alarm signal. Alternatively, press and hold 
the UP ARROW button for three seconds to clear the alarm signal and reset the latches.
 
 
ALARM2 LATCH: if an alarm condition occurs from the secondary sensor, the controller will continue to 
signal the alarm until reset, even if the alarm condition is cleared. Power to the controller must be turned 
off and then on again to turn off the alarm. Alternatively, press and hold the UP ARROW button for three 
seconds to clear the alarm and reset the latch.
 
 
ALARM1 LATCH: if an alarm condition occurs from the control sensor, the controller will continue to signal 
the alarm until reset, even if the alarm condition is cleared. Power to the controller must be turned off 
and then on again to turn off the alarm. Alternatively, press and hold the UP ARROW button for three 
seconds to clear the alarm and reset the latch.
 
 
Multi‐Speed Fan Control and control of other loads: The alarms can be used for controlling the hot‐side 
fan of a TE device at two different speeds. The low‐speed setting is useful for reducing noise when the 
demand for cooling is low. The high‐speed setting can be triggered when an alarm condition is sensed to 
maintain  cooling  performance  as  required.    Alarm  deadband  can  be  added  to  keep  the  fan  speed  from 
oscillating.    See  the  “Optional  Multi‐Speed  Fan  Control  Setup”  drawing  for  further  details.  Note:  each 
alarm output can handle other load types with up to 1 A of current draw.  The controller can handle up to 
20 A overall combines output and alarm current. 
 

Advertising
This manual is related to the following products: