TE Technology TC-48-20 User Manual

Page 55

Advertising
background image

55

25. ANALOG OUTPUT MULTIPLIER 

 

 

Write Command: 2f  

 

 

Read Command:  63 
Interpret: 

For writing, multiply desired analog output multiplier by 100

10

 then 

convert to hexadecimal. For reading, convert to decimal then divide by 
100

10

.

 

Allowable range is 0 to 1.00

10

1.00 multiplier is a value of 100

10

  

0.50 multiplier is a value of 50

10

  

0.00 multiplier is a value of 0  

 

26. LATCH CLEAR 

 

 

Write Command: 33  

 

 

Read Command:  NA 

 

 

Interpret: 

 

Send this command to reset alarm latches. 

 

27. OUTPUT ENABLE 

 

 

Write Command: 30  

 

 

Read Command:  64  

 

 

Interpret: 

 

0 = OFF 

 

 

 

 

 

1 = ON 

28. EEPROM WRITE ENABLE 

 

 

Write Command: 31 

 

 

Read Command:  65 

 

 

Interpret: 

 

0 = OFF 

 

 

 

 

 

1 = ON 

NOTE: this command valid only for firmware versions H and higher.  EEPROM WRITE ENABLE is 
automatically turned “ON” whenever the controller is turned on.  Note: for the TC‐48‐20 only, 
regardless of the EEPROM WRITE ENABLE setting, changes made to parameters via keypad are 
automatically stored in the EEPROM.  This feature can not be turned off. 

 

27. REVISION LEVEL 

 

 

Write Command: NA 

 

 

Read Command:  05  

 

 

Interpret: 

 

 08 = H 

 

 

 

 

 

 09 = I 

 

 

 

 

 

10 = J 

 

 

 

 

 

11 = K 

 

 

 

 

 

12 = L 

 

 

 

 

 

13 = M 

 

 

 

 

 

14 = N 

 

 

 

 

 

15 = O 

 

 

 

 

 

16 = P 

 

 

 

 

 

17 = Q 

 

 

 

 

 

18 = R 

 

 

 

 

 

19 = S 

 

 

 

 

 

20 = T 

 

 

 

 

 

21 = U 

 

 

 

 

 

22 = V 

 

 

 

 

 

23 = W 

 

 

 

 

 

24 = X 

 

 

 

 

 

25 = Y 

 

 

 

 

 

26 = Z 