2.3.8 TEMP OFFSET 
 

Values: ‐10.0 °C to +10.0 °C 

 

Default value = 0.0 °C 

 

Description: Offsets the control sensor value for both the display and control algorithm. 
 

2.3.9 ALARM 1 TEMPS 

Values: ‐20 to 199 or OFF for HIGH setting; ‐20 to 199 or OFF for LOW setting 
Default value for HIGH = 60 
Default value for LOW = ‐20 
 
Description: This sets the high and low temperatures for signaling an alarm based on the control sensor 
temperature.    Adjustments  are  in  1  °C  increments,  and  the  high  setting  must  be  higher  than  the  low 
setting. If the HIGH setting is increased past 199, OFF is indicated and no alarm will be signaled based on 
the  control  sensor  for  over‐temperature  conditions.  If  the  LOW  setting  is  decreased  past  ‐20,  OFF  is 
indicated and no alarm will be signaled based on the control sensor for under‐temperature conditions. 
 
Note: If the controller senses an open circuit or a short circuit on the control sensor, the controller will 
automatically turn off output power, regardless of the ALARM 1 FUNCTION setting. 
 

2.3.10 ALARM 1 FUNCTION 

Values: KEEP OUTPUT ON or TURN OFF OUTPUT 
Default value = TURN OFF OUTPUT 
 
Description:  This  setting  determines  what action  will  be taken  when  there  is  an alarm  condition  on  the 
control  sensor.  When  KEEP OUTPUT  ON  is  selected,  output power  to the  TE device stays  on during  the 
alarm  condition,  and  the  alarm  1  signal  on  JP5‐10  is  activated.  When  TURN  OFF  OUTPUT  is  selected, 
output power to the TE device is turned off, and the alarm 1 signal on JP5‐10 is activated. 
 

The  ALARM  1  and  ALARM  2  outputs  on  JP5‐10  AND  JP5‐11  will  momentarily  pulse  on  and  off 
several  times  in  the  first  second  after  the  controller  is  turned  on.    This  happens  as  the 
microprocessor in the controller configures itself, regardless of any alarm condition. 

 
2.3.11 ALARM 2 TEMPS 
 

Values: ‐20 to 199 or OFF for HIGH setting; ‐20 to 199 or OFF for LOW setting 

 

Default value for HIGH = 60 

 

Default value for LOW = ‐20 

 

Description:  This  sets  the  high  and  low  temperatures  for  signaling  an  alarm  based  on  the  optional, 
secondary sensor temperature.  Adjustments are in 1 °C increments, and the high setting must be higher 
than  the  low  setting.  If  the  HIGH  setting  is  increased  past  199,  OFF  is  indicated  and  no  alarm  will  be 
signaled based on the secondary sensor for over‐temperature conditions. If the LOW setting is decreased 
past  ‐20,  OFF  is  indicated  and  no  alarm  will  be  signaled  based  on  the  secondary  sensor  for  under‐
temperature conditions. 
 
Note:  If  the  controller  senses  an  open  circuit  or  a  short  circuit  with  respect  to  the  thermistor,  the 
controller  will  signal  an  alarm  condition  (presuming  it  is  not  set  to  OFF).  In  addition,  if  the  controller 
senses an open thermistor circuit, T2 will not be displayed in the primary screen. 

 

2.3.12 ALARM 2 FUNCTION 
 

Values: KEEP OUTPUT ON or TURN OUTPUT OFF 

 

Default value = TURN OUTPUT OFF 

 