10. ALARM1 TYPE  

 

 

Write Command: 27 

 

 

Read Command:  5b 

 

 

Interpret: 

 

0 no load effect. 

 

 

 

 

 

1 load off on alarm. 

 

11. ALARM2 TYPE  

 

 

Write Command: 2a 

 

 

Read Command:  5e 

 

 

Interpret: 

 

0 no load effect 

 

 

 

 

 

1 load off on alarm 

 
 

12. SENSOR CHOICE 

Write Command: 20 

 

 

Read Command:  54 
Interpret: 

 

0 = 15K sensor is selected. 

 

 

 

 

 

1 = 10K sensor is selected. 

 

 

 

13. CONTROL MODE 

 

 

Write Command: 21 

 

 

Read Command:  55 

 

 

Interpret:  

 

0 = COOLING mode. 

 

 

 

 

 

1 = HEATING mode. 

 

14. LOW SET RANGE 

 

 

Write Command: 22  

 

 

Read Command:  56  
Interpret: 

This is used to set the lowest temperature that the controller set point 
can be set to. 

 

15. HIGH SET RANGE 

 

 

Write Command: 23  

 

 

Read Command:  57  
Interpret: 

This is used to set the highest temperature that the controller set 
point can be set to. 

 

16. CONTROL SENSOR OFFSET  

       

 

Write Command: 24  
Read Command:  58 
Interpret: 

Value to offset control sensor in order to calibrate external sensor if 
desired. 

 

17. ALARM 1 LOW SETTING 

 

 

Write Command: 25  

 

 

Read Command:  59  
Interpret: 

Temperature reference to compare against control sensor for high 
alarm output. Temperatures are in whole degree increments.  To turn 
the low alarm OFF set the alarm temperature to ‐21

10

 (ffeb

16

). 

 

18. ALARM 1 HIGH SETTING 

 

 

Write Command: 26 

 

 

Read Command:  5a 
Interpret: 

Temperature reference to compare against control sensor for high 
alarm output.  Temperatures are in whole degree increments.  To turn 
the high alarm OFF set the alarm temperature to 200

10

 (00c8

16

). 

 