2.3.4 DERIVATIVE GAIN 
 

Values: 0.00 to 10.00 (cycles per minute) 

 

Default value = 0.00  

 

Description: This senses the rate of change of the temperature and allows the controller to anticipate the 
power needed to compensate for rapid changes in the system loading. The derivate gain is generally used 
on  very  sluggish  systems  or  where  very  quick  response  is  necessary.  It  works  in  a  similar  way  to  the 
integral gain, but it acts upon the change in the error, not the absolute error. 
 

2.3.5 SENSOR TYPE 
 

Values: 15K‐1 or 10K‐1 

 

Default value = 15K‐1 
 
Description:  
15K‐1  should  be  selected  when  using  the  supplied  MP‐3193  thermistor  or  other  thermistors  with 
equivalent temperature‐resistance curves. See Appendix for further details. 
 
10K‐1  should  be  selected  when  using  thermistors  equivalent  to  10  k‐ohm,  curve  “B”  temperature‐
resistance curve as defined by YSI Temperature, Inc. 
 

If you are using two thermistors, they must have the same resistance versus temperature 
characteristics. Also be sure that you have selected the correct sensor type. Otherwise a 
dangerous condition could exist because the actual temperature could be higher or lower than 
the temperature being interpreted by the controller. 

 

2.3.6 CONTROL MODE 

Values: COOL or HEAT 
Default value = COOL 
 
Description:  
COOL mode causes the controller to increase the output power when the control sensor temperature is 
greater than the set temperature. 
 
HEAT mode causes the controller to increase the output power when the control sensor temperature is 
less than the set temperature. (This mode can also be used with resistive heaters.) 
 
Note: If you are using a TE device in the cool mode and you want to switch to the heat mode, you must 
also switch the connection between JP4‐3 and JP4‐4. 
 

2.3.7 CONTROL RANGE 
 

Values: ‐20 to 199, applies to both HIGH and LOW settings 

 

Default value for HIGH = 070 

 

Default value for LOW = ‐20 

 

Description:  Sets  the  maximum  and  minimum  temperatures  available  in  the  SET  TEMPERATURE  menu.  
This is a safety feature that helps to limit the set point to the safe operating temperature of the system 
being controlled.  Adjustments are in 1 °C increments, and the high setting must be higher than the low 
setting. 
 
Note:  If the CONTROL RANGE is adjusted such that it is no longer inclusive of the SET TEMPERATURE, the 
controller  will  continue  to  control  to  that  SET  TEMPERATURE.    However,  once  you  scroll  to  the  SET 
TEMPERATURE menu, the SET TEMPERATURE will automatically reset to be within the CONTROL RANGE, 
and  the  output  power  will  adjust  accordingly.  The  SET  TEMPERATURE  can  then  only  be  set  within  the 
CONTROL RANGE. 